Energy Incident Register · Quarterly report

Everyone is watching batteries. The record says grid.

What 713 sourced safety incidents at battery, solar, wind and grid assets in 73 countries show, and what they cannot show. For the people who insure, broker, finance, build, own and operate them.

Q3 2026Entries 713Countries 73Every entry cites its sources

The public conversation about energy safety is almost entirely about battery fires. The register does not show that. Grid infrastructure accounts for nearly half of every incident recorded, and electrical faults outnumber fires.

This report sets out what the register holds, counted on 2026-09-25. It is deliberately explicit about what the numbers cannot tell you, because a safety record that overstates itself is worse than no record at all.

73
incidents occurred July to September 2026
5
of them major
713
entries in the register, 73 countries
80%
of all incidents in normal operation

This quarter73 incidents occurred between July and September

These are the incidents the register records as having happened in the quarter, by the date the reporting gives. 49 at grid infrastructure, 8 at solar pv, 5 at battery storage, 5 at wind (onshore), 4 at hybrid co-located, 2 at wind (offshore). 5 were major. 35 of the 73 are still provisional, published from first reports and rechecked automatically as more sources appear.

The 5 major incidents

RefWhenWhereIncident
EIR-0207JulyItalyMaintenance worker killed after being trapped in turbine blade mechanism in Italy
EIR-0201JulyCanadaTurbine nacelle destroyed by fire at Pubnico Point Wind Farm, Nova Scotia
EIR-1154SeptemberCubaCuba nationwide grid collapse follows high-voltage transmission line failure
EIR-1220SeptemberPuerto RicoExplosion and fire at Carolina substation leaves more than 217,000 without power
EIR-1223SeptemberUnited StatesBattery storage fire forces evacuations in Southern California

What it cost, where the reporting says

ConsequenceThis quarter, as reported
Deaths1 recorded
Injuries3 recorded
Evacuations10 incidents with an evacuation
Downtime stated1 incidents, 5 site days in total
Loss estimate statedNot stated for any incident
Regulatory action13 incidents

Consequences are recorded only where a source states them. Most reports state none, and the absence of a figure is recorded as an absence, not a zero.

Quarter by quarter

January to March37
April to June34
July to September73

Read a rise with care. The register widens its search as it goes, so part of any increase is the register seeing more, not the world producing more. 25 in July, 11 in August, 37 in September.

Significant incidents this quarter, a selection

RefMonthTechnologyCountrySeverityIncident
EIR-0212JulGrid infrastructureCubaSignificantFire at Alquízar substation cuts power to thousands in Artemisa
EIR-0228JulGrid infrastructureUnited KingdomSignificantFire at New Milton substation causes major rail service disruption
EIR-0730JulWind (offshore)GermanySignificantBlade failure on Vestas 15MW turbine at He Dreiht offshore wind farm
EIR-0191JulWind (onshore)United StatesSignificantThird turbine failure in three years at North Fork Ridge Wind Farm, Missouri
EIR-0200JulGrid infrastructureSpainSignificantTransformer fire cuts power to thousands in South Tenerife
EIR-0241JulGrid infrastructureUnited StatesSignificantTransformer fire cuts power to downtown Bangor apartment building during heat wave
EIR-0243JulGrid infrastructureUnited StatesSignificantTransformer fire burns for hours at Hunterstown generating station
EIR-0558JulGrid infrastructureUnited StatesSignificantSubstation transformer fire cuts power to F.E. Warren Air Force Base, Wyoming
EIR-0224JulGrid infrastructureBangladeshSignificantFire at Dhaka substation near FDC intersection cuts power for hours
EIR-0097JulBattery storageGermanySignificantBattery storage fire in Bautzen, Germany prompts local evacuations
EIR-0238JulGrid infrastructureUnited StatesSignificantUnderground transformer explosion at Conti and Bourbon Streets, New Orleans
EIR-0220JulGrid infrastructureUnited KingdomSignificantFire at Weymouth substation near coastal attraction cuts power
EIR-0196JulGrid infrastructureUnited StatesSignificantTransformer explosion in Hackensack sparks car fires, power outage
EIR-0195JulGrid infrastructureBahamasSignificantTransformer explosion at Blue Hills Power Station causes island-wide blackout in New Providence
EIR-0218JulGrid infrastructureUnited StatesSignificantConey Island transformer explosion sparks fire, cuts power to 900 homes
EIR-1175JulSolar PVUnited KingdomSignificantRooftop solar panel fire guts NHS mental health ward in Malton
EIR-0095AugBattery storageRomaniaSignificantOvernight fire at Stâlpu battery storage site prompts multi-agency response
EIR-0166AugGrid infrastructureNetherlandsSignificantLarge fire at Meeden high-voltage substation proves difficult to extinguish

18 of the 47 significant incidents. The full quarter, every entry with its sources, is in the register.

What failedThe component and the mode, where the reporting says

The most useful thing a record can say is what broke. News reporting says it less often than anyone would like, which is why not determined is the largest mode in every technology. Where it is stated, this is the pattern.

TechnologyComponent most often namedEntriesMode, where stated
Grid infrastructureTransformer55electrical fault 10, external event 5, the rest not determined (3 major)
Switchgear or breaker20electrical fault 6, external event 2, control or software 1, the rest not determined (6 major)
Wind (onshore)Blade9mechanical failure 1, human or procedural 1, external event 1, the rest not determined (3 major)
Nacelle or gearbox9electrical fault 2, mechanical failure 1, human or procedural 1, the rest not determined (4 major)
Battery storageCell or module26thermal runaway 7, electrical fault 3, the rest not determined (5 major)
Rack or enclosure6thermal runaway 1, the rest not determined (1 major)
Solar PVInverter or PCS5electrical fault 3, the rest not determined
Module or string4external event 3, electrical fault 1
Hybrid co-locatedCell or module11thermal runaway 4, the rest not determined (2 major)
Rack or enclosure5electrical fault 1, mechanical failure 1, thermal runaway 1, the rest not determined
Wind (offshore)Blade3external event 1, mechanical failure 1, human or procedural 1 (1 major)
Tower or foundation1mechanical failure 1

Finding 01Grid infrastructure is the largest category, by a distance

Substations, transformers, switchgear and transmission account for 336 of 713 entries. Battery storage, which dominates the coverage, accounts for 105.

Grid infrastructure336
Wind (onshore)138
Battery storage105
Solar PV85
Hybrid co-located31
Wind (offshore)18

Share of all published entries. Grid infrastructure is 47%, battery storage 15%.

Finding 02Electrical faults outnumber fires

302 entries are classified as electrical and 277 as thermal. Thermal runaway is the subject of most of the industry’s safety writing, and it is not the largest category in the record.

Electrical fault302
Thermal / fire277
Mechanical95
Other31
Near-miss4
Commissioning3
Gas release1

Finding 03Most incidents happen on an ordinary day

573 of 713 entries, 80%, occurred during normal operation. Commissioning, which absorbs a large share of attention in contract negotiation and in insurance wordings, accounts for 50 entries, or 7%.

Normal operation573
Not stated62
Commissioning50
Maintenance25
End-of-life3

Severity across all entries: 458 significant, 160 minor, 87 major, 8 near-miss.

The absence of precedent in your file is usually not evidence of low frequency. It is evidence that nobody aggregated it.

Finding 04The map shows where reporting happens, not where risk is

United States accounts for 255 entries and United Kingdom 100. United States is not 3 times more hazardous. It reports more incidents, in English, to outlets that are indexed and searchable.

CountryEntriesCountryEntries
United States255India26
United Kingdom100Germany22
South Korea52Canada21
South Africa41Not stated19
Australia26Taiwan10

73 countries in total. 19 entries have no country stated in their sources, and are recorded as such rather than guessed.

For anyone pricing or financing assets outside the English-speaking world, this is the practical point. A clean loss history for a region may describe the reporting, not the region.

Finding 05Battery storage incidents are flat in the record

Recorded battery storage incidents by year of occurrence: 6 in 2021, 11 in 2022, 16 in 2023, 11 in 2024, 18 in 2025, 15 in 2026 so far. Deployed capacity has grown steeply over the same period.

20216
202211
202316
202411
202518
2026 so far15

This is the finding we hold most loosely. It is consistent with the industry’s argument that battery safety has improved, and it is equally consistent with our coverage of battery incidents being better in some years than others. It is offered as an observation, not a conclusion, and the entries behind it are all public.

Named this quarterWho the reporting named, by role

Every name below appears because a source named it in that role for an incident this quarter. Being named is not a finding of fault. The largest suppliers appear most because they have the most equipment in the field and the most reporters who know their names.

Operators

NameIncidents
National Grid2
Bahamas Power and Light2
ScottishPower2
City Water and Light1
LS Power1
Versant Power1
Entergy New Orleans1
Duquesne Light1
Tees1
Con Edison1
Portland General Electric1
Electric Company of Artemisa1

Manufacturers

NameIncidents
Vestas1
Siemens Gamesa1
LG Energy Solution1

The verified recordEach incident this quarter, with what sits behind it

Empty cells mean no source states it. Nothing here is inferred.

RefDateSiteOperatorOEMIntegratorFailed elementRoot causeDowntimeLossRegulatorySources
EIR-02012026-07-21Pubnico Point Wind FarmNextEra Energy CanadaNacelle, hub and blades destroyed by fireNot reported; under investigation at time of reportingsingle source
EIR-02072026-07-21Aria del Vento wind farmBlade motor mechanismUnder investigation; reported that the worker was pulled into the motor mechanism of a turbine blade while performing maintenance at height, cause not yet officially determinedInvestigation opened by local Carabinieri (San Marco Argentano command) into circumstances of the accident and PPE compliancesingle source
EIR-11542026-09-18Cuba's National Electrical UnionHigh-voltage transmission linesHigh-voltage transmission line failure in central Cuba, reported as provisional pending further detail; broader system attributed to fuel shortages and ageing infrastructure.single source
EIR-12202026-09-24LUMA Energy substation in CarolinaLUMA Energysingle source
EIR-12232026-09-24single source
EIR-02432026-07-02Hunterstown Generating Station (Hunterstown Combined Cycle Generating Station)LS PowerTransformerNot determined at time of reporting; investigation ongoingsingle source
EIR-02412026-07-03Gallagher Place / Bangor House ApartmentsVersant PowerGround-mounted transformer near apartment buildingTransformer reportedly overheated, causing an electrical fire; described by fire officials as provisional causesingle source
EIR-02382026-07-04Underground transformer vault, corner of Conti and Bourbon StreetsEntergy New OrleansUnderground electrical transformerUnder investigation; Entergy stated the cause is believed related to a fire beneath the underground vault, provisional pending further engineering assessmentverified
EIR-02282026-07-07New Milton substationElectrical substation adjacent to railway trackNot reported.single source
EIR-11752026-07-08Springwood ward, Malton HospitalTeesRooftop solar panelProvisional: fire most likely started at one of the rooftop solar panels; extensive fire damage to the panels prevented determination of the specific ignition causesingle source
EIR-02242026-07-11Substation near FDC intersectionSubstation equipment, unspecifiedNot determined immediately; cause of the fire was not reported.single source
EIR-05582026-07-11F.E. Warren Air Force BaseSubstation transformerNot confirmed in reporting; base attributed outage to damage to critical components at the substation caused by a transformer firesingle source
EIR-02202026-07-12Weymouth substationNot statedNot reported in available sources.verified
EIR-02182026-07-15Con EdisonUtility pole and transformerNot reported; article states a wooden utility pole and transformer failed and exploded, but no official cause was given.single source
EIR-02122026-07-18Alquízar electrical substation (Kv 4000)Electric Company of ArtemisaSubstation (Kv 4000)Not determined at time of reporting; under investigation. No confirmed link to previously reported dielectric oil theft at the site.single source
EIR-00972026-07-21Cell or moduleNot determined at the time of reporting.verified
EIR-07302026-07-22He DreihtEnBWVestasTurbine bladeUnder investigation by Vestas and EnBW; not yet determinedRelevant authorities were notified immediately by EnBWsingle source
EIR-02002026-07-23Electrical transformer/network equipmentNot confirmed; officials believe insulating oil inside the transformer caught fire, contributing to the blaze, provisionalsingle source
EIR-01962026-07-29PSE&GDistribution transformerUnder investigation; cause of the transformer failure not yet determinedsingle source
EIR-01952026-07-30Blue Hills Power StationBahamas Power and Light15MVA transformerPreliminary investigation by BPL indicated a suspected underground cable fault caused the explosion of a 15MVA transformer; described as a preliminary finding.single source
EIR-01912026-07-31North Fork Ridge Wind FarmLiberty UtilitiesTurbine tower/base and blades; entrance door at base of turbine broken off, all blades on the groundNot reported; Liberty Utilities stated it was assessing the situation. A prior November 2023 incident at the same site was attributed to a lightning strike; cause of a January 2024 collapse not reported.single source
EIR-01882026-08-06Grammenitsa Extra High Voltage CenterPPCTransformer at extra-high-voltage substationNot reported; explosions occurred in a transformer, cause not stated by sourcesingle source
EIR-01672026-08-08Greater Changhua 4OrstedSiemens GamesaTurbine (specific component not identified)Under investigation at time of reportingRelevant authorities and stakeholders notified per statutory reporting requirementssingle source
EIR-01792026-08-14Jicotea substationElectric Union of Villa ClaraSubstation transformer and associated circuits (54 and 94)Fire at the substation, reportedly linked to a long history of recurring faults in ageing equipment (in service since 1965); underlying cause of the fire itself not specified by sources.5 dsingle source
EIR-01842026-08-15Bellshill substationScottishPowerNot statedNot reported.single source
EIR-01812026-08-17Tolosa power stationEdelapTransformerReported as a fire at the power station that caused a transformer to explode; underlying ignition cause not stated (provisional).single source
EIR-01762026-08-20AEP TexasSubstation equipment (unspecified)Not reported; cause of the fire had not been determined at time of reporting.single source
EIR-01702026-08-21Eastern SubstationVarious pieces of electrical equipment at the substation were damaged by the fire.Not confirmed at time of reporting; President stated the issue relates to the distribution network rather than the production sector. A formal investigation was ordered but no findings were reported in this source.President ordered a comprehensive and transparent investigation into the causes of the incident and directed the government to provide resources to accelerate repairs.single source
EIR-00952026-08-26Not statedNot reported.single source
EIR-01662026-08-29Meeden high-voltage substationTenneTSwitchgear or breakerNot reportedsingle source
EIR-06262026-09-02Lakeview Avenue electric substationVillage of MayvilleMini-transformers and a feeder line at the substationProvisional, as described by the village mayor: mini-transformers blew and one northside feeder failed, producing arcing and a small fire; full technical cause not yet determined at time of reporting.Mayville Village Board approved a resolution declaring a state of emergency to expedite repair of the substationsingle source
EIR-00922026-09-02RWESubstationNot reportedsingle source
EIR-00912026-09-03Hermes Road substationNational GridNot statedThought to be accidental, not formally confirmed at time of reportingsingle source
EIR-05542026-09-06Chinchwad Extra High Voltage SubstationMaharashtra State Electricity Transmission22 kV current transformer and breaker unitTechnical fault causing an explosion in a 22 kV current transformer and breaker unit, described as provisional by officialsverified
EIR-01612026-09-07Summerside Sunbank solar power farmCity of SummersideOne battery storage unit within a multi-unit battery energy storage systemNot reported; fire originated in one of several battery storage units at the sitesingle source
EIR-01652026-09-07otherUnder investigation, not established whether fire was accidental (technical fault) or deliberately started (arson); break-in at second site under separate investigation with cause unconfirmedPolice criminal investigation ongoing; nationwide search for a suspect linked to a series of attempted sabotage attacks on power infrastructuresingle source
EIR-07782026-09-08Central SubstationCity PowerUnderground cable tunnels / substation infrastructureUnder investigation; City Power suspects illegal activity in underground cable tunnels, including possible theft and vandalism, may have contributed to the firesingle source
EIR-06412026-09-10Bay Area Rapid TransitSubstationNot reported.single source
EIR-07792026-09-15Long Atip solar hybrid stationSarawak Energy BerhadBattery and inverter room (approximately 480 batteries)Not established at time of reportingMarudi Fire and Rescue Department stated further action would be taken by its operational team upon arrival at the station.single source
EIR-11572026-09-17Whitelee WindfarmScottishPowerTurbine nacelle and bladesNot yet determined; under investigation by ScottishPower at time of reportingScottishPower stated it notified the relevant authorities; no further regulatory action reportedsingle source
EIR-10392026-09-17Lambert Street 417 electricity substationMsunduzi ElectricityElectrical cables inside substationNot determined at time of reportingsingle source
EIR-10682026-09-18Mason Park substationAusgridCoil towerNot yet determined; investigation to begin once site is safe to accesssingle source
EIR-11532026-09-21KEPCO Power ICT Daejeon CenterKEPCO Power ICT Daejeon Center28 lithium-ion battery packs housed in two racksNot reported. Under investigation by police and fire authorities.Police and fire authorities are investigating the exact cause of the fire and the scale of the damage.single source
EIR-12222026-09-22Blue Hills Power StationBahamas Power and Lighttransformersuspected lightning strikeverified
EIR-11782026-09-22Metropolitan Water District facility, 3000 block of Wheeler AvenueMetropolitan Water Districtunknownsingle source
EIR-12262026-09-22A rat is mentioned as a possible cause (not confirmed)single source
EIR-11792026-09-22Georgia Power high-voltage substationGeorgia Powertransformernot determinedsingle source
EIR-11832026-09-22Subestación AméricaCorporación Nacional de Electricidadsingle source
EIR-11942026-09-23industrial zone of Yozgat centretransformerinvestigation opened into causesingle source
EIR-11822026-09-23transformersingle source
EIR-12242026-09-23Sabana Llana substationsingle source
EIR-12212026-09-24single source
EIR-02422026-07-02CWL substation near Turtle CreekCity Water and LightPotential transformer (PT transformer)Under investigation at time of reporting; utility spokesperson said extreme heat may have been a contributing factor but could not confirm this as the direct causesingle source
EIR-02402026-07-04Duquesne LightTransformerNot reportedsingle source
EIR-01712026-07-13Herrington Community Solar FarmAC/DC converterInvestigation determined an AC/DC converter failed and sparked, igniting the surrounding dry grass; the breaker tripped automatically as designed.Fire Chief and town code inspector required the operator to provide a letter confirming the system meets all applicable codes before the site could be restarted.single source
EIR-02142026-07-16PGE substation, 19th Avenue near Davis Street, CorneliusPortland General ElectricPiece of substation equipmentLightning strike or lightning-related electrical disturbance affecting substation equipment, causing it to catch fire; described as provisional as the story was developing at time of publication.single source
EIR-02062026-07-22PepcoCapacitor bank on the roof of the substationNot reported; cause of the fire was not immediately releasedverified
EIR-05572026-07-23Garriochmill Way / Henderson Street substationSP Energy NetworksElectrical substation equipmentDescribed by the operator only as a 'network fault'; cause not further specifiedsingle source
EIR-01992026-07-28National GridSubstation equipment (unspecified component)Substation overheated, as stated by fire service spokesperson; underlying cause not specified.single source
EIR-05722026-08-04BlueWave Asset ManagementSingle battery cabinetNot reported; described as a battery cabinet failuresingle source
EIR-01732026-08-21Bradwell-on-Sea wind farmWind turbine substationNot reportedsingle source
EIR-00962026-09-01Transformer, Rue Principale, ErnsterCreosTransformerNot reported. Creos stated the cause of the fire was yet to be determined at the time of reporting.single source
EIR-05502026-09-07Not statedNot reported.single source
EIR-05482026-09-07Mylapore substationTNPDCL230kV circuit breakerNot reported; a breaker in the substation exploded, cause not specifiedsingle source
EIR-11902026-09-07inverterUnauthorised inverter replacement by unqualified personnel in breach of equipment manualTwo individuals each received ten-day administrative detention under the Fire Protection Lawsingle source
EIR-01642026-09-08Substation in UtjehaMontenegrin Electricity Distribution SystemSubstationNot stated; local residents attribute it to a broader pattern of grid reliability problems including a prior pole fire and voltage fluctuations, but no official cause was reported.single source
EIR-06442026-09-09South Manheim SubstationPPLNot reported. The source states the cause of the fire was not immediately clear.single source
EIR-10832026-09-18White Hall substation service areaCentral Virginia Electric CooperativeUtility pole topNot conclusively stated; fire was found confined to the top of the utility pole, with the transformer itself intactsingle source
EIR-11362026-09-18Moss Landing Power Plant, Vistra battery energy storage facilityVistra EnergyLG Energy SolutionDamaged lithium-ion battery modules from the January 2025 fire, still present on site during demolitionNot stated for the September 2026 smouldering incident; occurred during EPA-overseen demolition of fire-damaged portions of the battery building to access severely damaged modules from the January 2025 fire. Damaged batteries remained charged despite being disconnected from the grid.EPA oversight of demolition and battery removal; ongoing air monitoring, sampling, fire and smoke watches, water collection and testing, battery temperature monitoring and dust suppressionsingle source
EIR-11982026-09-20Sirius Solarunder investigationsingle source
EIR-11882026-09-22single source
EIR-11812026-09-22Subestação CarajásEDPPresence of birds on the electrical networksingle source
EIR-11932026-09-23Eversource Energypole-mounted transformerUtility pole fell for unknown reason, causing oil to spill from pole-mounted transformer and ignite.single source

This table is the quarter’s slice of the verified dataset. The same rows export as CSV from your dashboard.

What to do with itThe same record, read from six chairs

The findings above are the same for everybody. What they mean depends on where you sit.

Underwriters

The exposure is in the operating period

80% of recorded incidents happened in normal operation and 7% at commissioning. The operational policy is carrying the risk that construction wordings are so carefully written to cover. Electrical faults outnumber fires, so a survey built around fire protection misses the larger category. And a clean loss history in a territory that does not report in English may be a record of the reporting, not of the risk.

Brokers

Placement is an argument. This is the evidence

When the market loads for battery fire, the record shows grid infrastructure at nearly half of all incidents and battery incidents flat across five years. Before renewal, check every manufacturer, integrator and EPC on the client’s schedule against the register, so nothing in the risk presentation surprises an underwriter who has already looked.

Lenders and investors

Check the names on the term sheet before close

Every company named in published reporting has a page, 353 of them, and 40 of the largest manufacturers are watched daily so that a company with no published incident has a page that says exactly that, which is an answer a credit committee can minute. And because most incidents occur in operation, the independent engineer’s construction-phase review is not the end of technology diligence.

Developers and EPCs

50 incidents happened at commissioning. Read them first

Each entry records what failed, and the standards where the reporting referenced them. It is the shortest route to a specification that has already learned from somebody else’s site, and to a supplier shortlist checked against something other than the supplier’s own references.

Owners, operators and O&M

What failed, what contributed, what was learned

Every entry carries those three things where the reporting gives them. Use them to set the inspection regime, to plan for the days after an incident when a site has not yet been handed back, and to bring a supplier’s published history into warranty and service agreement negotiations.

Fire services, regulators and researchers

The same fields on every entry, every source listed

Free to read and free to cite. Where a source does not state something, the record says so, so nothing has to be unpicked before it can be compared with anyone else’s data.

The paid recordWhat sits behind each entry

Everything in this report is drawn from the free register. Behind each entry, for subscribers, sits the structured record where a source supports it: the site, operator, owner, manufacturer, integrator and EPC; the root cause and the failed element; capacity, age at incident, downtime and loss estimate; and every source with its verification status. Team plans add CSV export of the verified dataset and this report in full each quarter. Enterprise adds the API and weekly bulk files.

That is where the questions this report raises get answered for a specific site, a specific supplier or a specific book. Three complete records are free, sent by email within a minute, so the depth can be judged before anything is paid for. Plans are on the plans page.

How much to trust itWhat each entry is built on

A record that does not say how solid it is invites the reader to guess, and readers guess generously. These are the register’s own figures for the 628 entries with a verified record behind them.

FieldEntriesShare
Two or more sources cited18630%
Corroborated by independent reporting8413%
Resting on one published source44270%
Failed element identified53585%
Operator named by a source41967%
Capacity stated16126%
Manufacturer named by a source11018%
Integrator named by a source335%

So: a count by technology or country rests on almost every entry and can be leaned on. A rate per GW rests on about a quarter of them. A cut by manufacturer rests on fewer than one in five, and by integrator on one in twenty. The register publishes those cuts, and it publishes these percentages next to them, so nobody has to find out the hard way.

What this report is not

652 of the 713 entries were published between 2026-07-01 and 2026-09-25. That is a new register working through an archive. It is not 652 incidents in a quarter, and nobody should report it as one.

By the year each incident occurred: 180 in 2026, 130 in 2025, 60 in 2024, 32 in 2023, 31 in 2022, 38 in 2021, 35 in 2020, 61 in 2019. Coverage of earlier years is partial and improving, so a rise across years in this register is a measure of the register, not of the world.

Grid infrastructure entries went from 10 in 2024 to 69 in 2025 to 110 in 2026. Grid failures did not multiply. The register’s coverage of them did.

MethodHow to check any figure in this report

  • Every entry is written from published reporting, and lists the sources it was written from. Any number here can be taken apart entry by entry.
  • Entries name the site, the town and the companies only where the source names them. A name a source does not give is a guess, and guesses are left out.
  • Incidents submitted confidentially through the site are anonymised absolutely and carry no site, company or product.
  • Where a source does not state something, the field records that it was not stated. Nothing is inferred from a photograph, a country or a technology.
  • Entries published from first reports are marked provisional and rechecked automatically as more sources appear.
  • Corrections are free and are made on request, whoever asks.

The register is independently run and self-funded. It takes no payment from any operator, vendor or service provider in the industries it covers.

Energy Incident Register

A public register of safety incidents at battery storage, solar, wind and grid assets. Free to read, free to cite.

Browse the register · Live benchmarks · Methodology · Corrections

Figures counted 2026-09-25 and correct as at that date. The register is updated daily, so the live figures will differ.

Cite as: Energy Incident Register (2026). Quarterly report, Q3 2026. energyincidentregister.com/reports/2026-q3