Data centre fires and power failures

As of 21 November 2026, the Energy Incident Register records 181 data centre incidents worldwide in 41 countries, 23 of them in 2026.

Counted from the register on 21 November 2026.

Key facts

Counts are of entries in published reporting, not rates. The register is new and has been filling in its archive, so a rise across years measures the register before it measures the world.

Every data centre incident in public reporting that started in the power systems: UPS and battery rooms, backup generators, switchgear, transformers and fuel. Each entry says what happened and lists its sources. Free to read.

Get the next data centre fire or power failure by email

181 entries so far, 55 since 2024. Confirm your email and the full list arrives as a spreadsheet (CSV): reference, year, country, what failed, what happened and the source for every entry. One email when a new incident is reported, at most two a day, plus a Monday digest. Free, no account needed, unsubscribe in one click.

Data centre incidents: a quick heads-up first, then the confirmed details.

We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By subscribing you agree to the privacy policy.

See what a full record shows →

One real record. The masked fields are in it:

Transformer failure and control fault cause Azure data centre power loss EIR-2254, 2026, United States

Operator
•••••••••
Root cause
•••••••••
The part that failed
•••••••••
Services that went down
•••••••••
Type of facility
•••••••••
Exact date
•••••••••
How long the outage lasted
•••••••••
See plans

Your email and a six-digit code; no card; once per person. Then a plan, or carry on with the free register.

Every data centre incident

Newest incident first. Search them, or narrow them by country, year or severity. Each entry is free to read, with what happened and its sources; the record behind it adds the cause where it is established, the part that failed, the downtime and the loss.

181 entries, showing the newest 20

See what failed, why, and what it cost

The record behind each entry: the manufacturer, integrator and operator, root cause, failure mode, downtime, losses and every source.

£39 a month

All 181 data centre incidents, with filters

For a data centre insurer, broker or operator team

Example

See what a record holds before you pay: two complete records are open to everyone.

The Energy Incident Register is a data contributor to the PV Fire Intelligence Network (PV-FIN), led by BRE. As cited by DatacenterDynamics.

181
Data centre entries
59
Fires
41
Countries
22
Classed major
55
Since 2024

What the record adds

Every entry on this page is free to read. The record behind each one adds the fields an analyst needs, read from the sources and checked against them. Across the 181 data centre entries it holds:

FieldEntries
Operator128 of 181
Root cause133 of 181
The part that failed126 of 181
Services that went down115 of 181
Type of facility (cloud, colocation, enterprise, government, telecom)130 of 181
Fire service response54 of 181
Exact date129 of 181
How long the outage lasted84 of 181
Battery chemistry5 of 181

The newest, with the record

EntryType of facilityOutageRoot cause
Electrical duct fire at Orange data centre in Val-de-ReuilNot statedNot stated••••••••••••••
Electrical overload triggers fire scare at identity agency data centreNot statedNot stated••••••••••••••
Power outages at Portuguese health data centre disrupt national prescriptionsNot statedNot stated••••••••••••••
Smouldering fire in battery system at Berlin data centreNot statedNot stated••••••••••••••
Drone attack reported to shut down Yandex data centre in Vladimir region, RussiaNot statedNot stated••••••••••••••
UPS battery fire in server room at Istiqlal Mosque, Jakarta••••••••Not stated••••••••••••••

What failed

Counted from the words of the reporting itself. An entry is counted under each part its reporting names, and "Not stated" means the public reporting did not say.

Part named in the reportingEntries
UPS and battery rooms74
Backup generators57
Switchgear and electrical rooms31
Transformers and substations19
Fuel systems6
Not stated56

By year

Year of the incidentEntries
202623
202518
202414
202316
202213
20217
20206
20199
201811
201710
201612
20156
20145
20134
201211
20116
201010

By country

CountryEntries
United States49
United Kingdom21
France12
Germany10
Australia10
South Korea9
Japan8
India6
Singapore4
Canada4
Nigeria3
Netherlands3
South Africa3
Russia2
Indonesia2
Belgium2
Brazil2
Italy2
Taiwan2
Portugal1
Norway1
Uganda1
Ireland1
Bahrain1
United Arab Emirates1
Hong Kong1
Egypt1
Sweden1
Nepal1
Bangladesh1
Malaysia1
Spain1
Iran1
Philippines1
Czech Republic1
Saudi Arabia1
Haiti1
China1
Switzerland1
Tanzania1
New Zealand1
Not stated5

The major incidents

The entries the register classes as major: the longest outages, the worst damage and the incidents where people were hurt.

ReferenceYearCountryEntry
EIR-19842026United StatesTransformer explosion near Vantage Data Centers injures worker in San Antonio
EIR-18962026United Arab EmiratesStrikes on Amazon Web Services UAE data centre cause fire and power loss
EIR-18932025South KoreaLithium battery fire at South Korean state data centre disrupts government services (National Information Resources Service)
EIR-18692025United StatesConstruction worker electrocuted at QTS data centre in Fayette County
EIR-18672025EgyptFire at Telecom Egypt data centre kills four and injures 26
EIR-18752024IndiaReported fire at a data centre disrupts Reliance Jio network across India
EIR-18512023FranceWater leak sparks battery room fire at Clichy data centre
EIR-18492023BelgiumFire at Proximus data centre disrupts emergency calls in Belgium
EIR-18472023BangladeshFire at Khawaja Tower data centres in Dhaka, Bangladesh
EIR-06292023FranceFire severely damages Maxnod data centre in Saint-Trivier-sur-Moignans, France
EIR-08882022South KoreaBattery room fire at SK C&C Pangyo data centre disrupts Kakao services (Naver)
EIR-18482021FranceOVHcloud data centre fire destroys SBG2 in Strasbourg
EIR-18372020United KingdomFaulty UPS knocks out power at London Docklands data centre
EIR-23432018AustraliaFire system test shuts down power at Reserve Bank of Australia data centre
EIR-22862018Saudi ArabiaGenerator fire at Mada payments network data centre disrupts Saudi payments
EIR-18452017United KingdomPower failure forces British Airways data centre outage at Heathrow
EIR-18822016United StatesElectrical failure and small fire at Delta data centre in Atlanta
EIR-23622014CanadaTransfer switch and UPS failures cause government data centre outage in Fredericton
EIR-18782014South KoreaFire at Samsung SDS data centre in Gwacheon during UPS expansion works
EIR-23172013TaiwanUPS battery fire cuts power to Chief Telecom data centre building in Taipei
EIR-23202012CanadaTransformer explosion and fire disrupts Calgary city services and IBM data centre
EIR-19822010United KingdomContractors fined after electrocution at Morgan Stanley Heathrow data centre

How often do data centre fires happen?

On this register: 16 incidents in 2023 (6 of them fires), 14 incidents in 2024 (6 of them fires), 18 incidents in 2025 (8 of them fires), and 23 so far in 2026. These are the incidents that reached public reporting, written up with their sources.

Two older figures are often quoted. Uptime Institute counted 11 fires among more than 8,000 incidents its members reported from 1994, under half a fire a year. An opinion piece in DatacenterDynamics counted 31 reports of data centre fires from June 2003 to March 2021. The counts differ because each list holds something different: Uptime's comes from its members, the DCD figure from news reports of fires, and this register from public reporting of fires and power failures in the power systems, kept up every day.

The major data centre fires

OVHcloud, Strasbourg, 2021 EIR-1848

At about 00:40 on 10 March 2021 a fire broke out in the power supply room of the SBG2 data centre on the OVHcloud site in Strasbourg. Firefighters reported electrical arcs, and power could not be isolated promptly, which the reporting links to the fire spreading. OVHcloud data centre fire destroys SBG2 in Strasbourg.

SK C&C Pangyo (Kakao), South Korea, 2022 EIR-0888

19 pm in a battery room on the third basement floor of the SK C&C data centre in Pangyo, Gyeonggi, South Korea. The batteries were used for backup power. Battery room fire at SK C&C Pangyo data centre disrupts Kakao services.

The state data centre in Daejeon, South Korea, 2025 EIR-1893

A fire broke out on the evening of 26 September 2025 in a server room on the fifth floor of the National Information Resources Service (NIRS) data centre in Daejeon, South Korea. Officials suspect the fire began when a lithium-ion battery exploded during maintenance work to move backup power battery modules to the basement. Lithium battery fire at South Korean state data centre disrupts government services.

Digital Realty SIN11, Loyang, Singapore, 2024 EIR-0116

A fire alarm was triggered at SIN11 Digital Loyang 1, a multi-storey data centre at 3 Loyang Way, Loyang, Singapore, operated by Digital Realty, after an explosion occurred in a lithium-ion battery energy storage system used for uninterruptible power supply, located in battery rooms on the third floor. Approximately 20 occupants evacuated before fire crews arrived, and all site workers were evacuated shortly after the alarm. Explosion and multi-day fire at SIN11 Digital Loyang 1 data centre, Singapore.

Maxnod, France, 2023 EIR-0629

A fire severely damaged the Maxnod data centre at Saint-Trivier-sur-Moignans in the Ain department of France on 28 March 2023, and the facility was taken offline. The 800 square metre building's structure was reported as compromised, and initial estimates said its network and electrical infrastructure was destroyed. Fire severely damages Maxnod data centre in Saint-Trivier-sur-Moignans, France.

Telecom Egypt, Cairo, 2025 EIR-1867

On 7 July 2025 a fire broke out in an equipment room at the Ramses switchboard of Telecom Egypt, on the seventh floor of a 10-storey building in the Ramses area of Cairo. The fire lasted for hours. Fire at Telecom Egypt data centre kills four and injures 26.

Almere, Netherlands, 2026 EIR-1887

A large fire broke out at the NorthC data centre on Rondebeltweg in Almere on 7 May. Emergency services responded with multiple appliances and ladder trucks. Fire at Almere data centre causes power loss and outages.

Reliance Jio, India, 2024 EIR-1875

On 17 September 2024, Yahoo Finance Singapore reported that a fire at a data centre had caused an India-wide outage for Reliance Jio users, citing an unnamed source. The report does not name the data centre, say where in India it was, or describe which equipment was involved. Reported fire at a data centre disrupts Reliance Jio network across India.

East London lead-acid battery fire, 2026 EIR-1889

In the early hours of Saturday 24 January 2026, a fire broke out in a battery room at a commercial building on Nutmeg Lane in Blackwall, east London. The building is a 13-storey tower housing a data centre. Lead acid battery fire at east London data centre tower.

Data centre fires by country

Lithium-ion and UPS battery fires

74 entries name the UPS, its batteries or the battery room, and 5 of all data centre entries name lithium-ion batteries; lead-acid UPS batteries appear too. Every UPS and battery room fire at a data centre, and the backup generator failures.

For underwriters: the record behind every data centre entry adds the operator, the root cause where it is established, the part that failed, the services that went down and how long the outage lasted. The week pass opens every record; Team suits an underwriting team.

Questions answered

How many data centre fires have there been?

The register holds 181 data centre incidents from public reporting, 2010 to 2026, in 41 countries. 59 of them are fires or thermal events; the rest are power failures, explosions, gas releases and electrical injuries in the power systems. These are the incidents that reached public reporting; many smaller ones never do.

What causes most data centre fires?

Where the public reporting names the part that failed, the most common is UPS and battery rooms (74 entries), followed by backup generators (57) and switchgear and electrical rooms (31). In 56 entries the reporting does not say what failed.

Do lithium-ion UPS batteries cause data centre fires?

5 entries name lithium-ion batteries, including Lithium battery fire at South Korean state data centre disrupts government services (EIR-1893, 2025); Battery room fire at Digital Realty data centre in Hillsboro, Oregon (EIR-0106, 2025); Explosion and multi-day fire at SIN11 Digital Loyang 1 data centre, Singapore (EIR-0116, 2024). Lead-acid UPS batteries appear too. Each entry gives the source for what was said.

Which data centre incidents were the most serious?

22 of the 181 entries are classed as major, among them Transformer explosion near Vantage Data Centers injures worker in San Antonio (EIR-1984, 2026); Strikes on Amazon Web Services UAE data centre cause fire and power loss (EIR-1896, 2026); Lithium battery fire at South Korean state data centre disrupts government services (EIR-1893, 2025). The full list is on this page.

Where do data centre fires happen most?

In the reporting the register has found, United States (49), United Kingdom (21), France (12) have the most entries. That partly reflects where data centres are built and where the press reports on them.

Is there a list of data center fires?

Yes. This page lists every data centre (data center) fire and power failure the register has published, 181 entries from 2010 to 2026, each with its sources, free to read and cite. It is rebuilt from the register as new incidents are published.

How often do data centre fires happen?

In public reporting, the register holds 16 incidents in 2023, 14 in 2024, 18 in 2025 and 23 so far in 2026, fires and power failures together; 59 of its 181 data centre entries are fires. Older figures are lower because they counted less: Uptime Institute counted 11 fires among its members' reports from 1994, and an opinion piece in DatacenterDynamics counted 31 fire reports from 2003 to 2021.

What was the biggest data centre fire?

The OVHcloud fire in Strasbourg (EIR-1848): At about 00:40 on 10 March 2021 a fire broke out in the power supply room of the SBG2 data centre on the OVHcloud site in Strasbourg. Firefighters reported electrical arcs, and power could not be isolated promptly, which the reporting links to the fire spreading. The SK C&C Pangyo fire in South Korea (EIR-0888) took down Kakao's services: 19 pm in a battery room on the third basement floor of the SK C&C data centre in Pangyo, Gyeonggi, South Korea. The batteries were used for backup power.

Have there been data centre fires in the UK?

Yes. The register holds 21 data centre incidents in the United Kingdom, 3 of them fires; the latest is Lead acid battery fire at east London data centre tower.

What this page covers, and what it does not

The register records incidents in a data centre's power systems, because those are the parts that share their failure modes with battery storage and the grid: lithium-ion and lead-acid UPS batteries, diesel generators and their fuel, switchgear and transformers. A software outage or a cooling fault with no fire or power failure is not recorded here.

Public reporting on data centre fires often names the operator but rarely the battery chemistry, the UPS make or the cause. The register does not guess them. Where a fire service, regulator or the operator states one, the entry carries it and says who said it.

If you run data centres or insure them and want a field added, tell us what it should be.

How the count has changed

DateEntriesCountriesWhere
12 October 20269326DatacenterDynamics published these figures from the register.
21 November 202618141Today, from the live register.

Counts change for three reasons: new incidents are added as they are reported, older incidents are added as the archive is worked through, and entries found to describe the same event are merged into one. On 12 October this page showed 92. One entry, a second write-up of the 2016 Global Switch GS2 power fault (EIR-1992), had been merged into EIR-1996 on the site, but the register's database and API still counted it until 13 October, so they gave 93.

For data centre operators, their insurers and lenders

A submission tells you what the broker chose to include. The register tells you what has been reported about the site, the operator and the equipment, with the source for every line, and an estimated cost and downtime range where no figure was published.

Free: what happened

Each entry: the site and operator where the source names them, what happened, the contributing factors, the lessons and every source. Never a person. A spreadsheet of the whole set arrives when you confirm an alert sign-up on this page.

The record: what failed and what it cost

For subscribers, the record behind an entry adds the cause where it is established, the part that failed, the downtime and the estimated loss with a confidence band. Two complete records are open to everyone.

Get three verified records free by email Check an operator's name

Modelling data centre power risk? Every data centre incident as data, by spreadsheet, weekly file or API: a free 20-record sample and a 3-month pilot.

Get the next data centre fire or power failure by email

181 entries so far, 55 since 2024. Confirm your email and the full list arrives as a spreadsheet (CSV): reference, year, country, what failed, what happened and the source for every entry. One email when a new incident is reported, at most two a day, plus a Monday digest. Free, no account needed, unsubscribe in one click.

Data centre incidents: a quick heads-up first, then the confirmed details.

We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By subscribing you agree to the privacy policy.

How to use this

Related: battery storage fires, solar farm fires, wind turbine fires and substation and transformer fires.