Data centreUgandaEIR-1983

MTN Uganda data centre power failure disrupts voice, data and mobile money

July 2026Published 4 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Companies named in the reporting of this entry (being named is not a finding of fault): MTN Uganda

On Sunday 5 July 2026, MTN Uganda said a major power failure at one of its data centres disrupted voice calls, mobile data and MTN MoMo mobile money services. Subscribers in different parts of Uganda reported being unable to make or receive calls, access data or complete mobile money transactions, and some bank transactions linked to MTN Mobile Money were also affected. The disruption began around midday and became more widespread from about 1 p.m., according to The Independent.

Prime Business Africa reported that the outage lasted more than eight hours. MTN Uganda said technical teams were working to restore all affected services and later confirmed that all services had been fully restored. MTN Uganda said it would compensate customers whose bundles expired unused during the interruption and that it had begun a review of the incident. Sanyu FM, citing engineers in a report summary, reported that one of six generators at the data centre malfunctioned, which caused the UPS to self-protect and block the complete power supply. The full Sanyu FM article was not reviewed.

MTN Uganda attributed the outage to a major power failure at one of its data centres. Sanyu FM, citing engineers in a report summary, reported that a malfunction in one of the six generators at the data centre led the uninterruptible power supply (UPS) to self-protect and block the complete power supply. The sources reviewed do not set out the cause of the generator malfunction. The Independent and Prime Business Africa report that the outage coincided with a separate disruption to a bank's digital platforms, and that social media speculation about a cyberattack was not confirmed by either company.

  1. Test generator paralleling and automatic transfer under load, so that the failure of a single generator does not lead to loss of the whole supply to the data centre.
  2. Review UPS self-protection and bypass settings to confirm that they do not disconnect the critical load when one power source fails, and that the design keeps N+1 redundancy after maintenance.
  3. Ensure that critical customer services such as payments have failover to a second site, and prepare clear, timely customer communications and compensation processes for major outages.

More lessons on outages, backup supply and restoration, electrical protection and isolation, from every incident on the register.

Published 2026-10-04. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents by year, free with a credit (PNG).