Google Cloud data centre power failure causes cooling outage

2026Published 5 Oct 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Companies named in the reporting of this entry (being named is not a finding of fault): Google Cloud

Three Google Cloud services experienced a 15-hour outage after a power failure in the datacentre serving the europe-west4-a zone. An electrical fault on the utility grid upstream of the datacentre disrupted electrical distribution gear and cooling equipment. The DRUPS back-up power system for one side failed to take over due to electrical component failures. A chiller controller dropped offline, the redundant chilled water source was unavailable due to construction, and temperatures reached 44°C, leading to machine shutdowns. Workloads were turned down to protect data.

Upstream utility grid fault, failure of DRUPS transfer due to component failures and load deployment discrepancy, chiller controller failure during voltage transient, redundant cooling source unavailable due to ongoing construction.

  1. Verify that managed services advertised as zone-resilient do not have single-datacentre dependencies.
  2. Ensure backup power transfer systems are tested under realistic transient conditions.
  3. Maintain redundant cooling sources even during construction work at facilities.

More lessons on outages, backup supply and restoration, from every incident on the register.