Google Cloud data centre UPS battery failure causes six-hour Ohio outage
Mar 2025Published 4 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in the United States, and an email when EIR-1986 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Google Cloud
What happened
On 29 March 2025 the us-east5-c zone of Google Cloud's US East region, centred on Columbus, Ohio, lost utility power. The uninterruptible power supply (UPS) system that should have bridged the gap until generators started suffered a critical battery failure and could not carry the load. Virtual machine instances in the zone lost power and went offline. The power outage and UPS failure also caused packet loss within the zone, affecting network communication, and made a limited number of storage disks unavailable.
Engineers were alerted at 12:54 Pacific time, diverted traffic away from the affected location where possible, and bypassed the failed UPS to restore power from a generator by 14:49. Most services recovered shortly afterwards, but some needed manual action for full recovery. The disruption lasted six hours and 10 minutes and affected more than 20 Google Cloud products, including Compute Engine, Cloud SQL and Persistent Disk.
Contributing factors
Google's incident report attributes the outage to a loss of utility power, which triggered a cascading failure within the UPS system, followed by a critical battery failure. The Register reports that the UPSes appear to have prevented generator power reaching the racks until they were bypassed. Google has not publicly identified the cause of the battery failure and says it is working with its UPS vendor, which it did not name.
Lessons learned
- Test UPS battery systems under realistic load, including the transfer to generator, because the battery is the link the design depends on during a utility failure.
- Ensure a failed UPS can be bypassed quickly and safely to generator supply, and rehearse that procedure so it does not depend on manual improvisation.
- Test failover of workloads to other zones and regions, since some services in this incident needed manual steps to recover.
- Map secondary dependencies such as storage, networking and control planes within a zone, because the effects of a power loss spread well beyond the power system itself.