On 11 September 2026, roughly 5,500 gallons of diesel fuel leaked from a storage tank at an Equinix data centre on Hartz Way in Secaucus, New Jersey, according to local reports. The fuel flowed into Anderson Creek, a tributary of the Hackensack River. Equinix...
Data centre incidents in the United States
Data centre incidents recorded in the United States, with what happened, the contributing factors and the lessons, each with its sources.
49 published entries. Newest first. Search and filter these in the register.
Get the next data centre incident in the United States by email
One email when a new incident is reported, at most two a day, plus a Monday digest. Free, no account needed, unsubscribe in one click.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By subscribing you agree to the privacy policy.
Every entry
Newest incident first. Search them, or narrow them by country, year or severity. Each entry is free to read, with what happened and its sources; the record behind it adds the cause where it is established, the part that failed, the downtime and the loss.
On 7 February 2026, one data centre within Microsoft's West US cloud region in California, United States, lost power. According to a post incident report that Microsoft published, an electrical failure in an on-site transformer caused the loss of utility...
A transformer explosion was reported at about 10:20 p.m. on Friday 27 February 2026 near Wiseman Boulevard and Luckenbach Road in San Antonio, close to Vantage Data Centers. Police said one construction worker was found with critical injuries. The transformer...
See what failed, why, and what it cost
The record behind each entry: the manufacturer, integrator and operator, root cause, failure mode, downtime, losses and every source.
About 200 gallons of diesel were spilled near the Meta Data Center compound in Altoona, Iowa, on 3 December 2025, during routine maintenance on an on-site generator. The generator was being serviced by Turner Construction Company, according to WHO 13 and the...
A published report says the Crystal City site, Zavala County data centre in Crystal City, Texas, United States operated by NFN8 Group, one of three sites leased by the operator, was damaged by a fire in the week between Christmas and New Year at the end of...
Four fire incidents were reported at the CTP-01 facility operated by Chirisa Technology Parks in Chesterfield County, Virginia. The company said the latest fire, on the Monday before a 12 September 2025 report, was caused by a single battery that caught fire....
A fire broke out in a room at the Chirisa Technology Parks data centre at 1401 Meadowville Technology Park, Chesterfield County, Virginia. The incident began at 8am on 20 August 2025. Chesterfield County Fire and EMS reported that the fire was contained to...
On 27 July 2025, at about 08:30 UTC, a utility power failure at the Akamai data centre at 165 Halsey Street, Newark, New Jersey, caused the loss of HVAC cooling. The data centre building remained operational, but temperatures rose and Akamai hardware...
A construction employee was reported to have been electrocuted while working at the QTS Data Center in Fayette County. The account, published on 29 June 2025, says this was on Saturday morning. Fire crews found medical staff performing CPR. Advanced life...
In May 2025 a fire broke out in a battery room at the Digital Realty data centre in Hillsboro, Oregon, United States, prompting a significant response from the local fire service. Crews arriving on scene found batteries alight, with the fire contained to a...
On 29 March 2025 the us-east5-c zone of Google Cloud's US East region, centred on Columbus, Ohio, lost utility power. The uninterruptible power supply (UPS) system that should have bridged the gap until generators started suffered a critical battery failure...
A major gas leak was reported at a QTS data centre site at 9540 Godwin Drive, just outside Manassas, Virginia, on 9 April 2025. Prince William County Fire and Rescue were dispatched after the leak was reported at 2:10pm local time. A fire service spokesman...
A fire occurred at a data centre on the West Side of San Antonio, Texas, near Potranco and Ingram Road. The incident began around 2 p.m. when a fuel line split during diesel refuelling of generators. Fuel contacted hot exhaust components and ignited. The fire...
On Thursday 15 August 2024 a fire broke out on the roof of 350 East Cermak Road in Chicago, Illinois, a multi-tenant carrier hotel data centre that Digital Realty owns and operates as its ORD10 facility. CBS Chicago reported that firefighters attended the...
On 26 March 2024 at 14:58 UTC, the PDX01 data centre in Portland, Oregon, lost all power, less than five months after an earlier outage at the same facility. Cloudflare says the loss followed a reportedly simultaneous failure of four Flexential-owned and...
On 2 November 2023 Portland General Electric (PGE) had an unplanned maintenance event that shut down one of the utility feeds into the Flexential PDX04 data centre near Hillsboro, Oregon. Flexential started its generators to supplement the lost feed and kept...
An electrical failure in one of the redundant uninterruptible power supply (UPS) units at the Evocative EWR1 data centre, formerly INAP, at 1 Enterprise Avenue in Secaucus, New Jersey, United States, caused the unit to start smoking and then to start a small...
A fire broke out at a Windstream data centre in Lincoln, Nebraska, on Saturday 2 September 2023. According to the reporting, the fire caused a transformer to short and explode, which took down power to the facility's two main switches. The backup generator...
On the late evening of Sunday 30 April 2023, fallen trees affected the grid connection supplying the on-site data centre at the University of Virginia in Charlottesville. The facility was designed to move automatically to a backup generator, but the backup...
On 14 February 2023 smoke was reported at a data centre in Boston, United States, used by Oracle NetSuite. According to a report in The Register, cited by Network World, the smoke came from electrical equipment in a power room at the site. The same report...