Diesel spill from Equinix Secaucus data centre tank reaches creek
Sept 2026Published 4 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in the United States, and an email when EIR-1976 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Equinix
What happened
On 11 September 2026, roughly 5,500 gallons of diesel fuel leaked from a storage tank at an Equinix data centre on Hartz Way in Secaucus, New Jersey, according to local reports. The fuel flowed into Anderson Creek, a tributary of the Hackensack River. Equinix staff detected the release, stopped it and brought in a specialist contractor to begin clean-up. The Secaucus Fire Department, the New Jersey Department of Environmental Protection and the Hudson Regional Health Commission were notified.
State officials said the diesel was contained in the creek and had not reached the Hackensack River, and that no water intakes in the area were thought to be affected. Clean-up was expected to take several days, and about 3,500 gallons had been recovered by the weekend after the leak was first reported. The total volume lost was not confirmed in early reports.
Contributing factors
A later investigation by Equinix reportedly found that two valves in the fuel filtration system had failed. Early statements attributed the leak to a computer glitch. The sources do not say how long the leak ran before it was detected.
Lessons learned
- Valves and sensors in fuel filtration and transfer systems for backup power need condition monitoring and alarms that alert operators to a failure before a release occurs.
- Bunding, drainage and containment around fuel tanks must be able to stop diesel reaching watercourses, and should be tested regularly.
- Early explanations of an incident should be checked against the root cause findings before they are published or relied on.
More lessons on detection and monitoring, from every incident on the register.
Source
Site page: Equinix (status, dates and other incidents)
Other entries that name Equinix
Other entries that name Secaucus
Published 2026-10-04. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.