UPS maintenance trip causes brief power outage at Equinix Manchester data centre

May 2022Published 12 Oct 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): Equinix

Equinix's MA1 data centre in Manchester Science Park, Manchester, United Kingdom, lost power on the morning of 24 May 2022. A customer status page reported that both A and B power feeds failed at about 10:03, while Equinix said load was transferred to generators. Internet Exchange, Metro Connect, Equinix Fabric and Equinix Connect services in Manchester were affected. One observer posting on Reddit reported customers on different providers in other parts of the UK going down for about ten minutes.

Equinix said the trip followed planned maintenance on the site's uninterruptible power supply (UPS) to replace one communications board. It said power was restored after a few milliseconds, with some services down for up to ten minutes while they rebooted.

Equinix said the trip followed planned UPS maintenance to replace a communications board. The cause of the trip was still under investigation with vendors when the reports were published. The site was described as having N+1 power redundancy.

  1. Treat planned work on UPS control boards as high-risk and confirm the transfer path to backup power before the work starts.
  2. Verify that a single control fault cannot take out both A and B power feeds, and test that isolation under maintenance conditions.
  3. Customers should test their failover arrangements and avoid depending on a single facility for network-critical services.

More lessons on outages, backup supply and restoration, electrical protection and isolation, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Published 2026-10-12. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents in the United Kingdom, by year, free with a credit (PNG).

Data centre incidents in the United Kingdom: 21 entries, with a free alert for the next one.

See UPS and battery room fires at data centres and backup generator failures at data centres.

Browse the full register or submit an incident.