Register / Data centre / EIR-2273
← Back to the list
Data centreSouth AfricaEIR-2273

Load shedding outage causes cooling failure at MTN Gallo Manor data centre, Johannesburg

June 2022Published 12 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): Eskom

During Stage 4 load shedding by Eskom, South Africa's grid operator, a cooling failure was reported at MTN's Gallo Manor data centre in Johannesburg. MTN said a power outage on the Wednesday afternoon affected one of its coolers at the site. MTN said the cooling system is redundant, did not fully shut down, and was fully restored within 45 minutes. Hosting firm Afrihost, which hosts some web servers in the facility, said the cooling failure damaged certain of its hosting servers, and that its disruption began at 09:07 local time on the day before the article was published.

Afrihost said email services and websites hosted through it were offline for upwards of thirty hours. At the time of reporting, Afrihost said 12.6 percent of affected servers had recovered.

Extended Stage 4 load shedding, with outages scheduled in blocks of two to four hours. MTN said its battery back-up at sites could not recharge sufficiently between outages, and that the outage schedule did not allow enough time for batteries to charge.

  1. Cooling plant that depends on grid power needs backup sized for repeated outages across a load-shedding schedule, not only for a single outage.
  2. Redundant cooling units can limit the impact of a single unit failure, but operators should confirm recovery times and whether hosted equipment tolerates a loss of cooling.
  3. Tenants in shared facilities should understand the power and cooling dependencies of the site they occupy and maintain their own continuity and customer communication plans.

More lessons on outages, backup supply and restoration, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
out of service for about •• daysShown in the record →Full estimate

Published 2026-10-12. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents by year, free with a credit (PNG).

Data centre incidents in South Africa: 3 entries, with a free alert for the next one.

Browse the full register or submit an incident.