Generator failure during load shedding causes data centre power feed outage
Feb 2024Published 12 Oct 2026Updated 14 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in South Africa, and an email when EIR-2263 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
What happened
At about 03:05 on 11 February 2024, the Johannesburg Stock Exchange (JSE) detected a power feed disruption at its colocation data centre in South Africa. According to the JSE's service notice, the site was being load shed when the generator on the B leg power feed failed to start. The batteries then depleted, and the B leg lost power. The outage lasted approximately 20 minutes. Customers with dual-feed power configurations were said to have lost one of their two feeds, so a complete power failure was not expected, but equipment with a single power supply connected to the B feed may have gone down. The notice listed equity, derivatives and colocation services as affected.
Contributing factors
The notice does not give the reason the generator failed to start. Dual-feed racks were designed to tolerate the loss of one feed, but single-supply equipment on the B feed was exposed to the outage.
Lessons learned
- Test generator start sequences under load shedding and grid loss conditions, and confirm that automatic transfer works.
- Alarm on generator start failure so staff can act before battery reserves run out.
- Audit customer equipment connected to a single feed, since dual-feed design does not protect single-corded devices.