Shock injury to apprentice at Illinois data centre battery cabinet busbar during construction

2024Published 27 Nov 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): Equinix

During construction of an Equinix data centre in Elk Grove Village, Illinois, United States, electrical work was under way in a room containing battery cabinets. Clune Construction was the general contractor and Continental Electric Construction Co. the electrical contractor. According to an administrative law judge's ruling as reported by ENR, Continental's general foreman agreed to run cables in the room as a favour to the client, which required contact with a busbar on top of the battery cabinets.

Veolia, the commissioning contractor, had reportedly told Continental's foreman that the cabinets would be de-energised. The ruling states that a technician from Vertiv reconnected a wiring harness in a universal power source without telling anyone, and that when the commissioning contractor closed the main breaker, the power source and downstream battery cabinets were energised. Shortly after, an apprentice working for Continental reportedly touched the busbar and received a shock from a 480 volt supply. The severity of the injury is not reported. Continental disputes responsibility for the violation.

According to the ruling as reported, six workers from four contractors were working on different equipment in the same room, and communication between them was poor. The wiring reconnection was not notified to others. OSHA's compliance officer said ten points should have been tagged under lock out/tag out; Continental contests the OSHA finding and says the wiring change was an unforeseeable act by another company's employee. The cable work was outside the contractor's completed scope and was carried out as a favour, and the de-energised assurance was given verbally.

  1. A verbal assurance that equipment is de-energised is not a substitute for lock out/tag out applied to every point of isolation before work begins.
  2. Any intervention on wiring or equipment in an energised system must be notified to everyone working in the area and recorded in the permit system.
  3. Work outside a contracted scope, even when done as a favour, needs its own risk assessment, permit and isolation check.
  4. Where several contractors share a room during commissioning, one person should control access, isolation and communication for the whole area.

More lessons on electrical protection and isolation, worker safety and safe systems of work, from every incident on the register.

Site page: Equinix (status, dates and other incidents)

Published 2026-11-27. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents in the United States, by year, free with a credit (PNG).

Data centre incidents in the United States: 51 entries, with a free alert for the next one.

See UPS and battery room fires at data centres and switchgear and electrical room fires at data centres.

Browse the full register or submit an incident.