In the early hours of Saturday 24 January 2026, a fire broke out in a battery room at a commercial building on Nutmeg Lane in Blackwall, east London. The building is a 13-storey tower housing a data centre. The London Fire Brigade received the first call at...
Data centre incidents in the United Kingdom
Data centre incidents recorded in the United Kingdom, with what happened, the contributing factors and the lessons, each with its sources.
21 published entries. Newest first. Search and filter these in the register.
Get the next data centre incident in the United Kingdom by email
One email when a new incident is reported, at most two a day, plus a Monday digest. Free, no account needed, unsubscribe in one click.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By subscribing you agree to the privacy policy.
Every entry
Newest incident first. Search them, or narrow them by country, year or severity. Each entry is free to read, with what happened and its sources; the record behind it adds the cause where it is established, the part that failed, the downtime and the loss.
A power outage at a privately owned data centre used by the Department for Environment, Food and Rural Affairs (Defra) affected several Defra digital services from 11 to 14 May 2024. One affected service was the Automatic Licence Verification System (ALVS),...
Equinix's MA1 data centre in Manchester Science Park, Manchester, United Kingdom, lost power on the morning of 24 May 2022. A customer status page reported that both A and B power feeds failed at about 10:03, while Equinix said load was transferred to...
See what failed, why, and what it cost
The record behind each entry: the manufacturer, integrator and operator, root cause, failure mode, downtime, losses and every source.
On Monday 10 January 2022, at about 1810 UTC, a critical power interruption struck Interxion's Hanbury Street facility, known as LON1, in East London. According to the operator, the interruption affected some of the mains control equipment and caused outages...
On 27 August 2020, a fire broke out in a supply room on the third floor of the Telstra London Hosting Centre at 6 Greenwich View Place, on the Isle of Dogs, London. London Fire Brigade sent four fire engines and around 25 firefighters and reported that only a...
On 18 August 2020 a power outage hit Equinix's LD8 data centre in the Docklands area of London, which hosts equipment used by the London Internet Exchange (LINX) and many internet providers. Equinix said the root cause was a faulty uninterruptible power...
On Saturday 27 May 2017 a power outage affected British Airways' Boadicea House data centre, a facility close to Heathrow Airport that was operated by CBRE Managed Services. Reports say the uninterruptible power supply (UPS) system did not keep the facility...
A brief power outage affected the tenth floor of the GS2 data centre operated by Global Switch in London, United Kingdom. Data Center Dynamics reported it on 10 July 2017. EX Networks, whose customers were affected, said in a status update that it was...
At about 6am on Monday 14 November 2016, internet connectivity was affected for a number of broadband ISPs after a fault developed in one of the Power Distribution Units (PDUs) at Telehouse North, a major data centre in London. The faulty unit produced smoke,...
On 10 September 2016, a high voltage fault in the cable end box of the output circuit breaker for one on-site diesel rotary uninterruptible power supply at the Global Switch 2 data centre in London interrupted power for 222 milliseconds. All customers lost...
On 20 September 2016, staff were evacuated from The Chess Building in Watford Business Park after a strong smell of burning was reported from one of the computer suites and the fire alarm sounded. Two crews from Watford attended at about 1pm and extinguished...
In late August 2016 a power outage at the Solihull data centre of software provider SSP disrupted its Pure Broking insurance platform. Brokers and underwriters in the UK and New Zealand lost access to emails, client records and transaction functions. SSP said...
On the morning of 20 July 2016, a power outage occurred at the 8/9 Harbour Exchange facility in London, also known as LD8, a former Telecity site now owned by Equinix. Equinix said the outage was caused by a problem with one of the facility's uninterruptible...
On 21 July 2016, a power failure at Telehouse North, a data centre in London's Docklands, disrupted internet services for BT and Plusnet customers across the UK. BT said the problem was a substantial power failure at one of its internet connection partners in...
On the afternoon of 17 November 2015, the Sovereign House data centre in London Docklands, operated by TelecityGroup, lost utility power at around 14:00. The facility appears to have failed to switch over to its backup generators. Power was restored but then...
A fire broke out shortly before 6am on 24 June 2015 on the fourth floor of Telephone House, a BT building on May Street in Belfast city centre. BT said the fire disrupted the electricity supply to the building, affecting a number of customers in its data...
A fault in the electrical system took the Level 3 Braham Street data centre in London offline on 10 July 2012. The outage began at about 03:30 GMT and power was restored by 09:00. Technicians found four scorched bus bars, according to an incident report...
On the night of 29 May 2012, Pulsant suffered a power disruption at its Maidenhead data centre that cut customer servers and firewalls off from the internet. During planned maintenance, an uninterruptible power supply (UPS) failed after a device swap. The...
On the morning of Wednesday 27 July 2011, Telecity's Meridian Gate data centre in London lost all mains power. Tenant C4L reported that the UPS and generator did not take over, taking all customers offline and breaking its 10G network ring. Telecity told C4L...
In October 2010, a subcontracted cable worker was electrocuted at Morgan Stanley's Heathrow data centre in Hounslow, near Heathrow airport, during an electrical upgrade. Balfour Beatty Engineering Services was carrying out multi-million-pound infrastructure...