Three Google Cloud services experienced a 15-hour outage after a power failure in the datacentre serving the europe-west4-a zone. An electrical fault on the utility grid upstream of the datacentre disrupted electrical distribution gear and cooling equipment....
Named in a role in 5 records, and mentioned in the text of 10 entries, between 2010 and 2026.
Being named is not a finding of fault. Counts are of records in published reporting, not rates, and the company's role is the one the sources give.
Work at Google? See every record that names it, free, and ask for a correction or add your side.
Records naming this company
Free entries that mention Google
A fire at a third-party data centre triggered an emergency power shutdown of networking equipment. The incident isolated a local point of presence in Delhi and reduced network capacity across the metropolitan area. Google Cloud reported intermittent network...
On 29 March 2025 the us-east5-c zone of Google Cloud's US East region, centred on Columbus, Ohio, lost utility power. The uninterruptible power supply (UPS) system that should have bridged the gap until generators started suffered a critical battery failure...
See what failed, why, and what it cost
The record behind each entry: the manufacturer, integrator and operator, root cause, failure mode, downtime, losses and every source.
On 23 October 2024 at 18:22 US/Pacific time, an electrical arc flash occurred in one of the power distribution units serving the europe-west3-c zone of Google Cloud's Frankfurt region in Germany. The fault caused a partial power outage in a single data...
On 25 April 2023, a cooling system water pipe leak occurred at the Global Switch data centre in the Clichy commune of Paris. The leak originated in a non-Google part of the facility and entered a UPS battery room, where it caused a fire. Google Cloud reported...
In a July 2022 report, a blade was said to have become partially detached from a GE Cypress turbine at the Björkvattnet wind farm in central Sweden. The report described the farm as Google-contracted and said this was the second blade failure at the project...
An arc flash occurred at the Google data centre in Council Bluffs, Iowa when three workers were accessing an electrical cabinet. The workers sustained injuries and were taken to a local hospital, where they were reported in stable condition. Google stated...
At 09:19 PDT on 13 August 2015, four successive lightning strikes hit the local utilities grid supplying Google's European data centre in St. Ghislain, Belgium, within the europe-west1-b zone. The strikes caused a brief loss of power to storage systems...
On Wednesday 11 April 2012, a circuit breaker on the first-floor west side of the Telehouse 2 (TH2) data centre on boulevard Voltaire, Paris, tripped at 10:17. Power was restored at 10:53. Telehouse said that customers supplied at 48V or with dual feeds were...
On 24 February 2010 a power failure occurred at Google's primary data centre used by App Engine, the company's cloud application platform. Google did not disclose the cause of the failure. When power was lost, about 25 percent of the servers in the facility...