Water leak sparks battery room fire at Clichy data centre
Apr 2023Published 2 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in France, and an email when EIR-1851 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Global Switch, Google Cloud
What happened
On 25 April 2023, a cooling system water pipe leak occurred at the Global Switch data centre in the Clichy commune of Paris. The leak originated in a non-Google part of the facility and entered a UPS battery room, where it caused a fire. Google Cloud reported that the fire required evacuation of the facility, a response from the local fire department, and a shutdown of power to the whole building for several hours.
Google Cloud reported that the building's fire suppression water supply ran out at 22:45 US/Pacific, and that the battery room fire was reported extinguished at 04:11 US/Pacific on 26 April 2023. The europe-west9 Google Cloud region was affected. Regional control plane services lost quorum after one of the three buildings in the region was powered down, causing widespread outages across more than 100 services. Global Cloud Console operations were also affected until the region was removed from visible regions. Services were largely restored by 26 April 2023, with the incident ending at 20:00 US/Pacific.
Contributing factors
A cooling system water pump or pipe failure released water into the building. The water reached the UPS battery room and ignited a fire. Google Cloud reported that its regional control plane database replicas were not correctly distributed across the three buildings in the region, so quorum was lost when one building was powered down. The fire suppression water supply ran out during the fire. Battery room access was restricted during firefighting, which delayed recovery. Water and soot contamination required one cluster to be decommissioned.
Lessons learned
- Keep water-bearing cooling pipework and pumps out of or away from rooms containing UPS batteries, and fit leak detection that alarms before water reaches electrical equipment.
- Confirm that fire suppression water supply can sustain a prolonged battery room fire, since the supply here ran out during the event.
- Distribute control plane and quorum-critical replicas across independent buildings so that the loss of one building does not disrupt the whole region.
More lessons on detection and monitoring, fire suppression and firefighting, from every incident on the register.
Source
Site page: Global Switch (status, dates and other incidents)
Published 2026-10-02. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.