Data centreFranceEIR-1851

Water leak sparks battery room fire at Clichy data centre

Apr 2023Published 2 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Companies named in the reporting of this entry (being named is not a finding of fault): Global Switch, Google Cloud

On 25 April 2023, a cooling system water pipe leak occurred at the Global Switch data centre in the Clichy commune of Paris. The leak originated in a non-Google part of the facility and entered a UPS battery room, where it caused a fire. Google Cloud reported that the fire required evacuation of the facility, a response from the local fire department, and a shutdown of power to the whole building for several hours.

Google Cloud reported that the building's fire suppression water supply ran out at 22:45 US/Pacific, and that the battery room fire was reported extinguished at 04:11 US/Pacific on 26 April 2023. The europe-west9 Google Cloud region was affected. Regional control plane services lost quorum after one of the three buildings in the region was powered down, causing widespread outages across more than 100 services. Global Cloud Console operations were also affected until the region was removed from visible regions. Services were largely restored by 26 April 2023, with the incident ending at 20:00 US/Pacific.

A cooling system water pump or pipe failure released water into the building. The water reached the UPS battery room and ignited a fire. Google Cloud reported that its regional control plane database replicas were not correctly distributed across the three buildings in the region, so quorum was lost when one building was powered down. The fire suppression water supply ran out during the fire. Battery room access was restricted during firefighting, which delayed recovery. Water and soot contamination required one cluster to be decommissioned.

  1. Keep water-bearing cooling pipework and pumps out of or away from rooms containing UPS batteries, and fit leak detection that alarms before water reaches electrical equipment.
  2. Confirm that fire suppression water supply can sustain a prolonged battery room fire, since the supply here ran out during the event.
  3. Distribute control plane and quorum-critical replicas across independent buildings so that the loss of one building does not disrupt the whole region.

More lessons on detection and monitoring, fire suppression and firefighting, from every incident on the register.

Site page: Global Switch (status, dates and other incidents)

Published 2026-10-02. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents in France, by year, free with a credit (PNG).

Data centre incidents in France: 12 entries, with a free alert for the next one.

See UPS and battery room fires at data centres.

Browse the full register or submit an incident.