OVHcloud data centre fire destroys SBG2 in Strasbourg

Mar 2021Published 2 Oct 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Companies named in the reporting of this entry (being named is not a finding of fault): OVHcloud

At about 00:40 on 10 March 2021 a fire broke out in the power supply room of the SBG2 data centre on the OVHcloud site in Strasbourg. Firefighters reported electrical arcs, and power could not be isolated promptly, which the reporting links to the fire spreading. The building and about 30,000 servers were destroyed, and the adjacent SBG1 was terminally damaged. No one was hurt. A second, smaller fire later affected the battery room of SBG1.

Reporting of the firefighter and industrial-risk investigations notes high moisture readings near an inverter before the fire, recent maintenance on a UPS, a wooden ceiling and floors, uninsulated electrical ducts, and power that remained live after isolation attempts, including automatic start of backup generators. The fire was apparently not impeded by sprinklers or other suppression, and the free-cooling airflow is described as having acted like a chimney once the fire was established. The exact ignition source has not been confirmed in the available reporting.

  1. Data centre designs that use natural ventilation need fire-stop measures so airflow does not accelerate fire spread.
  2. Power isolation and backup-generator controls need to allow a rapid, reliable shutdown during an electrical fire.
  3. Fire compartmentation and suppression should be checked against the actual materials and layout, not assumed performance.

More lessons on spacing, layout and fire spread, electrical protection and isolation, fire suppression and firefighting, from every incident on the register.

Published 2026-10-02. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents in France, by year, free with a credit (PNG).

Data centre incidents in France: 12 entries, with a free alert for the next one.

See UPS and battery room fires at data centres.

Browse the full register or submit an incident.