OVHcloud data centre fire destroys SBG2 in Strasbourg
Mar 2021Published 2 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in France, and an email when EIR-1848 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): OVHcloud
What happened
At about 00:40 on 10 March 2021 a fire broke out in the power supply room of the SBG2 data centre on the OVHcloud site in Strasbourg. Firefighters reported electrical arcs, and power could not be isolated promptly, which the reporting links to the fire spreading. The building and about 30,000 servers were destroyed, and the adjacent SBG1 was terminally damaged. No one was hurt. A second, smaller fire later affected the battery room of SBG1.
Contributing factors
Reporting of the firefighter and industrial-risk investigations notes high moisture readings near an inverter before the fire, recent maintenance on a UPS, a wooden ceiling and floors, uninsulated electrical ducts, and power that remained live after isolation attempts, including automatic start of backup generators. The fire was apparently not impeded by sprinklers or other suppression, and the free-cooling airflow is described as having acted like a chimney once the fire was established. The exact ignition source has not been confirmed in the available reporting.
Lessons learned
- Data centre designs that use natural ventilation need fire-stop measures so airflow does not accelerate fire spread.
- Power isolation and backup-generator controls need to allow a rapid, reliable shutdown during an electrical fire.
- Fire compartmentation and suppression should be checked against the actual materials and layout, not assumed performance.
More lessons on spacing, layout and fire spread, electrical protection and isolation, fire suppression and firefighting, from every incident on the register.
Source
Other entries that name Strasbourg
Published 2026-10-02. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.