Data centreFranceEIR-2200

OVHcloud shuts Strasbourg data centre after battery room smoke

Mar 2021Published 10 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): OVHcloud

On Friday 19 March 2021, at about 6.50pm local time, OVHcloud staff at its SBG1 data centre in Strasbourg, France, identified smoke in a battery room that was not connected to the data centre's power systems. The company said the smoke came from batteries that were being stored in that room and had been damaged in a fire at the neighbouring SBG2 data centre earlier that month. As a precaution, the power supply to SBG1 and SBG4 was cut off, operations on site were paused, and most staff and partner teams were asked to leave, leaving security, fire safety and maintenance personnel on site.

Firefighters located the source in the battery room and the incident was contained within minutes. Two security personnel affected by the smoke were examined by medical professionals as a precaution. OVHcloud later decided not to restart SBG1 and to move its servers to other sites.

Batteries stored in an unconnected battery room had been damaged in a fire at the neighbouring SBG2 data centre on 9 March 2021. The sources give no further detail on the storage conditions or the nature of the battery fault.

  1. Batteries damaged in a fire can continue to produce smoke or heat, so they should be assessed and isolated rather than treated as inert stored equipment.
  2. Fire-damaged sites need a plan for stored batteries and equipment, including in rooms not connected to live systems.
  3. Precautionary isolation of power, with clear staff evacuation and return procedures, limits risk while fire services confirm the source.
  4. Smoke detection in battery rooms gives early warning and should be linked to an agreed, rehearsed response.

More lessons on electrical protection and isolation, worker safety and safe systems of work, detection and monitoring, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Published 2026-10-10. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents in France, by year, free with a credit (PNG).

Data centre incidents in France: 13 entries, with a free alert for the next one.

See UPS and battery room fires at data centres.

Browse the full register or submit an incident.