Aug 2024Published 2 Oct 2026Updated 13 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in the United States, and an email when EIR-1876 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Digital Realty
What happened
On Thursday 15 August 2024 a fire broke out on the roof of 350 East Cermak Road in Chicago, Illinois, a multi-tenant carrier hotel data centre that Digital Realty owns and operates as its ORD10 facility. CBS Chicago reported that firefighters attended the former R. R. Donnelley printing plant in the afternoon, with reports of a carpet fire inside and a fire on the roof. Digital Realty described a minor fire on the roof and said reports of a carpet fire inside were unfounded.
ColoHouse, a tenant, said the fire occurred during a routine generator test, when hot smoke on the roof caused roof debris to catch fire. The Chicago Fire Department extinguished the fire quickly. Digital Realty reported no downtime and no customer impact, and no injuries were reported. The fire department did not order a mandatory evacuation.
Contributing factors
According to a ColoHouse spokesperson, hot smoke from a routine generator test reached the roof and ignited roof debris. Temporary roof repairs and water removal followed. The sources do not describe any further investigation.
Lessons learned
- Keep roofs near generator exhausts clear of combustible debris, and check exhaust routing and clearances before scheduled tests.
- Tell the local fire service in advance when generator tests are planned, so that smoke from a test is not mistaken for a fire.
- Keep customer load transfer and monitoring running during tests, and check roof areas for ignition after any exhaust release.