UPS inverter damage and control board faults cut power at Newark data centre

July 2018Published 13 Oct 2026Responsible editor: Chief Editor

Estimated damageModelled by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
out of service for about •• daysShown in the record →Full estimate

At about 19:35 UTC on 18 July 2018 utility power to the colocation data centre in Newark, New Jersey, housing Linode's US-East deployment was interrupted, and the critical load transferred to generator. The UPS system alerted the colocation provider to a possible failure, and technicians found that one unit in the N+1 UPS set had been damaged and taken offline for repair. The system continued in an N configuration. At 23:04 UTC, when power was switched back from generator to utility, the two remaining UPS units failed to take the load and transferred to bypass, causing a power loss of about three minutes. Power was fully restored at about 23:07 UTC. Most infrastructure and customer instances were back online by about 02:34 UTC on 19 July 2018.

The colocation provider's investigation found that a power surge during the utility failure damaged the inverter on one UPS unit. The provider stated that the remaining UPS units were unable to handle the load during the retransfer to utility power because of a control board malfunction, and went into bypass mode.

  1. Test UPS retransfer behaviour under load, since a system that runs on generator or in a reduced configuration may fail when switching back to utility power.
  2. Surge protection and inspection after a utility failure can reveal damaged power electronics before they cause a second outage.
  3. Replacing a faulty component on one unit is not enough if sibling units share the same control board fault; audit and replace common components across the set.
  4. Review power circuit redundancy for critical hardware after a power event.

More lessons on outages, backup supply and restoration, electrical protection and isolation, maintenance, inspection and ageing assets, from every incident on the register.

Published 2026-10-13. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents in the United States, by year, free with a credit (PNG).

Data centre incidents in the United States: 49 entries, with a free alert for the next one.

Browse the full register or submit an incident.