Fire damages transformer at Egbin substation
2025Published 1 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on grid infrastructure incidents in Nigeria, and an email when EIR-1697 is updated. No account needed; unsubscribe in one click.
Confirm your email and every substation and transformer incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Transmission Company of Nigeria
What happened
The Transmission Company of Nigeria said a fire at Egbin Power Plc at about 6:30 a.m. on a Tuesday affected its 150MVA 330/132/33kV Inter-Bus Transformer II at the Egbin Transmission Substation. The fire started in a service transformer owned by Egbin Power and connected to the 33kV side of that transformer. Preliminary investigations traced the fire to a faulty 33kV instrument transformer (CT/VT) installed by Egbin Power. The incident damaged the TCN transformer, with oil leaking from a tear in its main tank.
A load of 47MW was affected. Bulk supply was temporarily reduced to the Ikorodu and Odogunyan 132/33kV substations and to Sagamu Lines 1 and 2 and Maryland Line 2 in Lagos State. The load was diverted to the substation's second 150MVA transformer, which was reported to be operating under strain, and load-shedding followed.
Contributing factors
TCN said preliminary investigations traced the fire to a faulty 33kV instrument transformer (CT/VT) installed by Egbin Power. The full cause has not been independently confirmed.
Lessons learned
- Instrument transformers on the lower-voltage side of inter-bus transformers need regular inspection, because a fault there can damage the main transformer.
- Isolation and protection between a power station's service transformers and transmission assets should be checked so a station-side fault does not cascade.
- Spare capacity or a rapid replacement plan for a critical substation transformer limits how long customers face load-shedding.
More lessons on maintenance, inspection and ageing assets, electrical protection and isolation, outages, backup supply and restoration, from every incident on the register.