Fire damages transformer at TCN substation in Alagbon, Lagos

June 2023Published 28 Nov 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): Transmission Company of Nigeria

A fire broke out on a Wednesday afternoon, reported by Ripples Nigeria on 14 June 2023, at about 16:32 at the 300MVA 330/132/33kV substation of the Transmission Company of Nigeria (TCN) in the Alagbon area of Lagos. The fire affected one of the 60MVA power transformers at the station. According to TCN's statement, the operator on duty heard a heavy bang from the switchyard and found fire under the transformer's cooling fans and fins.

Staff tried to put the fire out with the substation's fire extinguishers, but oil leaking from the transformer ignited it further. The engineer switched off power to the 300MVA transformer and called the Federal Fire Service and the Lagos State Fire Service. The fire was put out at 17:35. TCN said the transformer could be salvaged or repaired, and that normal supply to the station was restored at 19:25, with all transformers in the station back in service.

Not reported. TCN's statement does not give a cause for the fire. It describes oil dripping from the transformer, which fed the fire and made it harder to control with extinguishers.

  1. Fit oil-filled transformers with an automatic fire suppression or deluge system, so that a fire is not left to manual extinguishers.
  2. Provide containment and drainage for transformer oil, so that a leak does not feed or spread a fire.
  3. Keep fire services' contact details and site access routes current and rehearse the response, so that they can be called and reach the site quickly.
  4. Arrange alternative transformer capacity and switching so that supply can be restored within hours while a damaged unit is assessed.

More lessons on fire suppression and firefighting, spacing, layout and fire spread, outages, backup supply and restoration, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
supply cut for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Published 2026-11-28. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Grid infrastructure incidents in Nigeria, by year, free with a credit (PNG).

Grid infrastructure incidents in Nigeria: 25 entries, with a free alert for the next one.

Substation and transformer fires: the counts, the latest entries and a free alert for the next one.

Browse the full register or submit an incident.