Utility cable fault drains UPS and blacks out National Park Service data centre in Denver
Jan 2014Published 12 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in the United States, and an email when EIR-2296 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Microsoft, Xcel Energy
What happened
On 1 January 2014, at about 3pm, the National Park Service data centre in Denver, Colorado, lost utility power and went completely dark. According to a note posted on the agency's website, the outage was caused by an underground cable that had either suffered water seepage or been affected by rodents. The agency's note blamed the local power provider, Xcel Energy. The building's uninterruptible power supplies (UPS) kept the facility running for about 30 minutes after utility power was lost.
The note made no mention of backup generators. Power was restored about two hours after the building went dark. The agency's note said the hardware in the data centre had been damaged and that about a third of the data had been corrupted. The note also said Microsoft had advised that restoring from backup tapes alone would not resolve the problem and that, in most cases, the environment would need to be rebuilt.
Contributing factors
The agency's note attributed the utility outage to an underground cable affected by water seepage or rodent invasion. The way the two utility power feeds were re-energised was cited in the note as one reason for the damage. An automatic shutdown process was cited by the agency as a cause of file corruption. High temperature in the data centre before shutdown was cited as a further reason for the damage. The UPS gave only about 30 minutes of runtime, and no backup generators were mentioned.
Lessons learned
- Test and document how facility loads transfer between utility feeds and UPS, and how feeds are re-energised after an outage, so that restoration does not add damage.
- Confirm that backup generation exists and is fuelled where UPS runtime, here about 30 minutes, would not cover a utility outage of this length.
- Set and test automatic shutdown and temperature thresholds so that equipment and data are protected in an orderly way, and keep backups that can restore a system without a full rebuild.
More lessons on outages, backup supply and restoration, from every incident on the register.
Source
Other entries that name Denver
Published 2026-10-12. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.