Electrical distribution failure during generator transfer causes Microsoft data centre outage in Netherlands
Oct 2023Published 12 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in the Netherlands, and an email when EIR-2266 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Microsoft
What happened
On 20 October 2023 Microsoft detected instability on the utility grid, in the form of voltage sags and swells, at one of its data centres in the AZ-01 Availability Zone of its West Europe region in the Netherlands. The company decided to transfer the load from the grid to backup generators. During this transfer a critical failure occurred in a section of the electrical distribution system, which prevented 10 percent of the generators from taking load.
The main distribution system went offline and the redundant system could not be accessed, and about 1 percent of server racks in the zone lost power. Services including App Service, Cosmos DB, SQL DB, Storage and Virtual Machines were affected between 07:31 and 09:15 UTC. Five storage scale units were hit. One needed hardware diagnostics and part replacements on about 5 percent of its storage nodes, and full restoration was complete by 17:10 UTC. The nature and cause of the distribution failure were not detailed.
Contributing factors
Voltage sags and swells on the utility grid prompted the transfer to generators. The source states that an issue with generator startup also led to an outage for some racks. The nature and cause of the distribution failure were not detailed.
Lessons learned
- Test generator transfer sequences under load so that faults in the distribution path are found before a grid disturbance forces a transfer.
- Verify that redundant distribution paths are independent and remain accessible during a fault, not only on paper.
- Plan storage recovery so that a single slow scale unit does not extend restoration for dependent services.
Source
Published 2026-10-12. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.