Hybrid co-locatedSouth KoreaEIR-0136

Fire and explosion at solar-linked BESS in South Korea

Jan 2022Published 7 Sept 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate
From the recordAsset hidden years oldThe maker is named in 8 other entries (being named is not a finding of fault)
Where
Singok-ri, Umyeon-myeon, Gunwi-gun, Gyeongsangbuk-do
Manufacturer
Willings supplied the power conversion system and LG Energy Solution the battery
What
Fire at outdoor BESS linked to 500 kW solar plant, followed by explosion
Injuries
None reported
Response
Firefighters entered after smoke reports; explosion ten minutes after they withdrew

Companies named in the reporting of this entry (being named is not a finding of fault): LG Chem, LG Energy Solution

A fire occurred at an outdoor energy storage system connected to a 500 kW solar power plant in Singok-ri, Umyeon-myeon, Gunwi-gun, Gyeongsangbuk-do. The system comprised a 450 kW power conversion system supplied by Willings and a 1.5 MWh lithium-ion battery supplied by LG Chem, now LG Energy Solution, and had been in commercial operation since August 2018. Firefighters entered the structure after reports of smoke. Ten minutes after they withdrew, an explosion occurred. No injuries were reported.

The system was operating at 90 per cent state of charge. Firefighters opened the door to the structure. A gas fire-extinguishing system, water system and exhaust were fitted.

  1. Firefighters should not open the door of a lithium-ion BESS on smoke reports alone, as this can allow air to trigger explosion.
  2. A gas fire-extinguishing system may not stop explosion in a BESS at 90 per cent state of charge.
  3. Operators should give fire services response manuals for the exact BESS model before any incident.

More lessons on fire suppression and firefighting, from every incident on the register.

  • Cause of the fire and explosion
  • Downtime and cost of repairs
  • Battery cell model and exact age

This entry is updated when these are reported. Get an alert for the next one like it.

Published 2026-09-07. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.