Fire and power outage take Colt Milan data centre offline
July 2015Published 13 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on data centre incidents in Italy, and an email when EIR-2318 is updated. No account needed; unsubscribe in one click.
Confirm your email and every data centre incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Colt
What happened
On Monday 6 July 2015 a fire closed Colt's Milan Lancetti Data Centre in Milan, Italy, taking the company's cloud services offline for several hours. Colt said it had experienced utility power supply outages at the site, that the vast majority of customer services had been fully restored and that the utility power supply was stable. Social media posts showed the facility completely dark, with smoke rising from the building and firefighters on site.
A report cited in the coverage said the fire may have been caused by overheating in the building's power infrastructure, but this was not confirmed. Temperatures in Milan had reached about 38 degrees C in the days before the incident. The Tier III site has 4MVA of power available. Reported outage durations differed, with one trade publication citing nine hours and one affected user citing about two hours.
Contributing factors
Colt reported utility power supply outages. A possible overheating fault in the building's power infrastructure was suggested by reports but not confirmed. Local temperatures were high at the time, but the sources do not link them to the fault.
Lessons learned
- Operators should verify that building power infrastructure, including switchgear and distribution equipment, is inspected and thermally monitored, particularly during heatwaves.
- Fire detection and suppression in electrical rooms should be tested to limit damage and prevent a single fault from taking a whole facility offline.
- Communication plans should give customers accurate and timely information about outage causes and durations, avoiding gaps that rely on social media posts.
More lessons on weather and external hazards, detection and monitoring, outages, backup supply and restoration, from every incident on the register.
Source
Site pages: Data Center, Keppel Data Centres | Milan Data Centre (status, dates and other incidents)
Other entries that name Milan
Published 2026-10-13. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.