Power lines start holiday fire in Goleta
July 2018Published 2 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on grid infrastructure incidents in the United States, and an email when EIR-1838 is updated. No account needed; unsubscribe in one click.
Confirm your email and every substation and transformer incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Southern California Edison
What happened
Electrical wires owned by Southern California Edison, combined with high winds and tree branches, started a fire on 6 July 2018 at around 8:30 pm in the Goleta foothills. Sundowner winds reached 30 mph as temperatures rose during the evening. The fire destroyed 10 homes and 13 other structures, damaged three homes and burned 113 acres, forcing evacuation of much of the foothills and a wildlife rescue. Trees and poles stood on private property at the top of Fairview Avenue.
Neighbours reported a bright flash, fire climbing a power pole and power fluctuations. Amperage fluctuations began at 8:17 pm with power lost at 8:41 pm. The first fire call came at 8:38 pm. Investigators ruled out lightning, camping, cigarettes and other human causes. Vegetation clearance around the wires had last been performed in April 2018.
Contributing factors
High winds of 30 to 40 mph, low humidity around 9 percent, temperatures of 100 to 108 degrees and tree branches close to the wires contributed to ignition. Previous vegetation maintenance occurred on 3 April 2018.
Lessons learned
- Maintain greater clearance between overhead lines and vegetation in high-wind areas.
- Monitor real-time amperage and smart-meter data for early detection of anomalies.
- Review vegetation management frequency after extreme heat and wind events.
More lessons on maintenance, inspection and ageing assets, detection and monitoring, weather and external hazards, from every incident on the register.