Battery fire at Damyang Solar Power Plant ESS marks fifth South Korean ESS fire of 2022
Dec 2022Published 11 Sept 2026Responsible editor: Chief Editor
- Where
- Damyang Solar Power Plant ESS, Deokgok-ri, Mujeong-myeon, Damyang-gun, Jeollanam-do
- Manufacturer
- Samsung SDI
- What
- Fire broke out in the battery room
- Response
- Damyang Fire Department sent 22 appliances and 150 firefighters
- Outcome
- 9.1 MWh battery system and power conversion equipment damaged
Get the next one by email
Free alerts on battery storage incidents in South Korea, and an email when EIR-0657 is updated. No account needed; unsubscribe in one click.
Confirm your email and every battery storage incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Samsung SDI
What happened
A fire broke out in the battery room of the Damyang Solar Power Plant ESS, an energy storage system co-located with a solar power plant in Deokgok-ri, Mujeong-myeon, Damyang-gun, Jeollanam-do. The facility manager was alerted by an abnormal alarm from the ESS monitoring equipment at around 15:32 and found smoke leaking from the battery room, with no visible flames. The fire department was notified immediately. Damyang Fire Department dispatched 22 fire appliances and about 150 firefighters.
The onboard carbon dioxide suppression system had activated before crews arrived, and water was applied to control the blaze. Because stored energy in the battery continued to release heat, full extinguishment was expected to take around three days. The 9.1 MWh battery system and associated power conversion equipment were damaged. This was reported as the fifth ESS fire in South Korea in 2022 and the 38th cumulative ESS fire incident in the country since 2017.
Contributing factors
The battery had reportedly undergone a prior intervention roughly two years before the fire, when manufacturer Samsung SDI replaced batteries and retrofitted additional capsule-type fire suppression equipment following a period of frequent ESS fires nationally. The specific technical trigger for this event (battery cell fault versus other equipment fault) was not confirmed in the source reporting.
Lessons learned
- Smoke or alarm detection without visible flame should trigger immediate isolation and fire service notification, as battery room fires can develop with limited external warning signs.
- Retrofitted suppression and battery replacement after earlier fires do not eliminate recurrence risk, so ongoing monitoring remains necessary.
- Suppression systems should be designed for extended thermal runaway events, since full extinguishment of a battery fire can take considerably longer than typical response timeframes.
More lessons on detection and monitoring, fire suppression and firefighting, from every incident on the register.
Not yet known
- Specific technical trigger for the event
- Battery model and age
- Cost of the damage
This entry is updated when these are reported. Get an alert for the next one like it.