Battery cabin fire at Hainan agri-PV storage station
May 2024Published 29 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on hybrid co-located incidents worldwide, and an email when EIR-2612 is updated. No account needed; unsubscribe in one click.
Confirm your email and every battery storage incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
What happened
A fire broke out on 26 May 2024 in a lithium iron phosphate (LFP) battery prefabricated cabin at a 70 MW agricultural photovoltaic (agri-PV) plus storage station in a city in Hainan, China. No casualties were reported. A fire-investigation analysis published by BJX on 13 November 2024 attributes ignition to a short circuit in a distribution box under a battery cluster. This entry is based on the headline and feed summary only; the full article could not be retrieved, so the response, the extent of damage, any downtime and the operator are not recorded.
Contributing factors
According to the fire-investigation analysis as summarised in the feed, ignition was attributed to a short circuit in a distribution box under a battery cluster. No other contributing factors are reported.
Lessons learned
- Treat distribution boxes and cabling beneath battery clusters as a short-circuit risk and include them in routine inspection.
- Provide cluster-level fault detection and isolation so that a short circuit can be contained before it ignites a battery cabin.
- After any thermal event in a prefabricated cabin, commission a full fire-investigation analysis and share its findings with other operators of hybrid sites.
More lessons on maintenance, inspection and ageing assets, detection and monitoring, investigation and fleet-wide checks, from every incident on the register.
Source
Other entries that name Hainan
Published 2026-10-29. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.