Register / Data centre / EIR-3073
← Back to the list
Data centreFranceEIR-3073

Scaleway Paris data centre transformer trips, generators keep power on

2019Published 27 Nov 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): Scaleway

On a September night, monitoring alerted the operator Scaleway at 05:09 that one power lineup at a Paris data centre was no longer supplied by the grid after a power transformer shut down. The automatic switchover to generators had already worked, and the lineup stayed powered by two generators while engineers attended. Staff found an oil leak at the transformer's Buchholz relay, a protection device that monitors temperature, oil level and gas.

The transformer was likely short of oil, by only a few litres. The team isolated the high-voltage unit, sourced vegetable oil during the night, replaced the relay, topped up the oil, purged air from the system and returned the transformer to service after about 10 hours. The company reported no customer impact. The article says the same incident had occurred three times in ten years. The article does not state the year of this incident.

The transformer was likely short of oil. The oil loss was traced to a leak at the Buchholz relay. The source does not give a root cause for the relay failure.

  1. Monitor transformer oil level, temperature and gas alarms in real time, so that a leak is seen before the transformer trips.
  2. Keep spare protection relays and the correct transformer oil on site, or under a fast supply agreement, to shorten repair time.
  3. Confirm that automatic transfer to generators works and that generator fuel autonomy is adequate before a fault occurs.
  4. Where oil-filled transformers sit near critical loads, use fire-resistant retention tanks that also contain leaks.

More lessons on detection and monitoring, electrical protection and isolation, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Published 2026-11-27. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents in France, by year, free with a credit (PNG).

Data centre incidents in France: 13 entries, with a free alert for the next one.

See backup generator failures at data centres.

Browse the full register or submit an incident.