Internal cable fault triggers substation fire alarm and CBD power outages in Auckland

Aug 2024Published 25 Nov 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
supply cut for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Companies named in the reporting of this entry (being named is not a finding of fault): Vector

On the evening of Saturday 24 August 2024, an internal cable fault at the Hobson Street substation in Auckland triggered a smoke alarm, and sprinklers in a high voltage switch room were activated at about 5.09pm. Fire and Emergency New Zealand attended with six fire trucks, two ladder trucks and a specialist command vehicle at the peak of the response. Power went out in several areas of the central business district, centred on Nelson, Halsey, Wellesley and Custom streets, at around 5.15pm.

Vector said the alarm dispatched emergency services and its crews automatically. After Fire and Emergency cleared the site, Vector crews entered, isolated the fault and restored power. The fire was extinguished at around 6pm, and Vector crews remained on site while the alarm was reset. The disruption to supply also caused the 1News 6pm bulletin to go off air for about three seconds.

Vector attributed the event to an internal cable fault. No further cause, equipment age or maintenance history has been reported.

  1. Automatic alarm activation at substations dispatches emergency services, so operators should agree clear site-clearance and re-entry procedures with fire services in advance.
  2. Isolating faulted equipment quickly once the site is cleared limits the area affected by an outage, as occurred here.
  3. Cable terminations and connections in high voltage switch rooms are worth monitoring and inspecting, since internal cable faults can trigger fire protection systems.

More lessons on worker safety and safe systems of work, electrical protection and isolation, detection and monitoring, from every incident on the register.

Published 2026-11-25. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Grid infrastructure incidents in New Zealand, by year, free with a credit (PNG).

Grid infrastructure incidents in New Zealand: 10 entries, with a free alert for the next one.

Substation and transformer fires: the counts, the latest entries and a free alert for the next one. Also: power line and cable failures.

Browse the full register or submit an incident.