Grid infrastructureNew ZealandEIR-1086

Flashover at Haywards substation cuts power to 94,000 Wellington homes

Mar 2020Published 18 Sept 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
supply cut for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden
Where
Haywards substation in Lower Hutt
Operator
Transpower
What
Electrical arc flashover during routine maintenance switching
Injuries
None reported
Cause
Human error during the switching procedure

Companies named in the reporting of this entry (being named is not a finding of fault): Transpower

During routine maintenance switching at the Haywards substation in Lower Hutt, incorrect earthing was applied, causing an electrical arc flashover reported initially as an explosion, with a loud bang and smoke. Transpower stated no equipment caught fire and nothing physically exploded, while a Fire and Emergency spokeswoman said there had been a small explosion in the switchyard. Protection systems automatically cut supply. The fault caused a widespread outage across the Hutt Valley, Wairarapa and parts of Wellington, affecting about 94,000 properties.

Train services on the Hutt line were suspended, traffic signals failed on State Highway 2, and water and wastewater utilities activated backup generators while asking residents to conserve water. Power was restored within roughly two hours, with restoration work completed by mid-morning. No injuries were reported. Transpower said the cause was believed to be human error during the switching procedure.

Incorrect earthing applied during routine maintenance switching at the substation, attributed by the operator to human error.

  1. Incorrect earthing during substation switching can trigger an arc flashover, so operators must add independent verification of earth connections before energising.
  2. A substation fault can cut power to 94,000 properties and disrupt trains, traffic signals and water utilities, so critical infrastructure needs tested backup supplies.

More lessons on worker safety and safe systems of work, outages, backup supply and restoration, from every incident on the register.

  • Exact sequence of the human error
  • Switchgear model and age
  • Cost of the outage and damage

This entry is updated when these are reported. Get an alert for the next one like it.

Published 2026-09-18. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Grid infrastructure incidents by year, free with a credit (PNG).

Grid infrastructure incidents in New Zealand: 5 entries, with a free alert for the next one.

Substation and transformer fires: the counts, the latest entries and a free alert for the next one.

Browse the full register or submit an incident.