Oil leak at Torness substation prompts beach warnings
2022Published 5 Oct 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on grid infrastructure incidents in the United Kingdom, and an email when EIR-2011 is updated. No account needed; unsubscribe in one click.
Confirm your email and every substation and transformer incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): SP Energy Networks
What happened
An electrical fault at Torness substation within the grounds of EDF’s Torness nuclear power station, operated by SP Energy Networks, activated an automatic fire protection system. The local authority said this led to a mix of transformer oil and cooling water overflowing into the drainage system. An environmental regulator said firewater and cooling oil were released to a site drainage system and that an unknown quantity escaped to the sea.
Authorities advised people not to enter the water at local beaches near Torness, East Lothian, to keep pets out of the water, and not to fish near the plant for at least the next 24 hours while water quality investigations continued. Clean-up teams used spill kits to block drains and collect oil. The initial oil release was reported to have been contained in a bund.
Contributing factors
The local authority said an electrical fault caused the automatic fire protection system to operate, and that cooling water then carried transformer oil beyond the bund into the drainage system. How much reached the sea was not reported.
Lessons learned
- Check that substation bunds and drainage can hold firewater as well as oil under fault conditions.
- Notify local authorities quickly if a release may reach the sea, so bathing and fishing advice can be issued while tests are pending.
- Keep a joint clean-up plan with the site operator, the network operator and the environmental regulator for oil and cooling-water overflows.
More lessons on maintenance, inspection and ageing assets, emergency response and public communication, from every incident on the register.
Source
Site page: Torness Substation (status, dates and other incidents)
Published 2026-10-05. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.