Lithium-ion battery container explodes and burns at French poultry farm
Published 29 Nov 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on hybrid co-located incidents in France, and an email when EIR-3106 is updated. No account needed; unsubscribe in one click.
Confirm your email and every battery storage incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
What happened
Shortly after 6 p.m. an explosion followed by a fire occurred in a lithium-ion battery container coupled with a photovoltaic power system at a poultry farm with capacity for 40,000 poultry. The container held 400 lithium-ion batteries of 50 kg each, described as able to store 1.4 MW. The fire produced large volumes of black smoke visible from several kilometres away, and the overpressure was felt in homes about 200 metres away.
The electricity supplier cut power to the area, leaving 700 people without electricity for one hour. The explosion destroyed a 180 cubic metre water tank and blew out windows of nearby houses. Eight people were looked after by emergency services before returning home. With the operator's agreement, firefighters first cooled the container and tried to abate noxious gases rather than attacking the burning batteries. Overnight monitoring was carried out with a technician present.
The next morning firefighters extinguished the fire with a fog nozzle over several hours, and it was declared out at about 2 p.m. The photovoltaic energy storage system was destroyed.
Contributing factors
The fire was apparently due to overheating of one battery, which led to thermal runaway and production of hydrogen in an enclosed container. A water tank was placed a few metres from the container. It was destroyed in the explosion and could not be used for firefighting, and responders could not connect to several 5 cubic metre tanks.
Lessons learned
- Water supplies for firefighting should be sited well away from battery containers, since an explosion can destroy a tank placed nearby.
- Enclosed battery containers need ventilation or explosion venting and gas detection, because thermal runaway can release flammable hydrogen.
- Operators and emergency responders should agree plans in advance covering water access, connection points, cooling strategy and monitoring after a battery fire appears to be out.
More lessons on fire suppression and firefighting, detection and monitoring, from every incident on the register.
Published 2026-11-29. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.