Frozen pressure sensors and substation fire blamed for Nashville outages

2022Published 24 Nov 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
supply cut for about •• daysShown in the record →Full estimate

Companies named in the reporting of this entry (being named is not a finding of fault): Nashville Electric Service, Tennessee Valley Authority

Over the 2022 holiday period, during extreme cold (the source gives no exact date), the Tennessee Valley Authority (TVA) said pressure sensors on two large generators at its Cumberland City Fossil Plant froze in sub-zero temperatures. TVA said the sensors tripped an automatic shut-off, reducing the power the units could produce, which contributed to rolling blackouts across the mid-state. About an hour later, Nashville Electric Service (NES) said a fire broke out in a building at its Cane Ridge substation, involving rows of electrical communication equipment, and thousands of homes in the Antioch and Cane Ridge areas lost power.

Many residents reportedly lost power for a full day. NES said a relay appears to have stuck and overheated without clearing the fault, which it believes caused the fire. Both utilities said full investigations were continuing.

Sub-zero temperatures froze pressure sensors on two generating units at the Cumberland City plant. At the Cane Ridge substation, NES believes a relay stuck, overheated and did not clear, which led to the fire. The utilities' explanations are preliminary.

  1. Operators should verify freeze protection and heat tracing for pressure sensors and instrumentation before extreme cold arrives.
  2. Protection relays need regular testing so that faults are cleared and cannot escalate into fires in control buildings.
  3. Utilities should give regular, scheduled updates to customers, lawmakers and the media during prolonged outages.

More lessons on detection and monitoring, electrical protection and isolation, outages, backup supply and restoration, from every incident on the register.

Site page: Cumberland Substation (status, dates and other incidents)

Published 2026-11-24. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Grid infrastructure incidents in the United States, by year, free with a credit (PNG).

Grid infrastructure incidents in the United States: 481 entries, with a free alert for the next one.

Substation and transformer fires: the counts, the latest entries and a free alert for the next one.

Browse the full register or submit an incident.