Generator fire reported at Upper Kotmale hydropower plant, Sri Lanka

Oct 2026Published 20 Nov 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate

The Daily Mirror reported that the Unit No. 2 generator at the Upper Kotmale hydropower station, near Thalawakelle in the central highlands, caught fire on the night of 16 October 2026, according to plant employees and an electrical superintendent. The superintendent said a spark at the breaker followed from a loose connection, and that the fire caused extensive damage to the generator rotor and rotor poles, with about 25 to 30 per cent of the stator burnt.

Plant staff estimated losses at Rs 600 to 800 billion, but another engineer said it was too early to estimate the cost of repair and rejected that figure. The station has two 75 MW units. The Energy Minister's media secretary told the newspaper that no turbine at the station had caught fire. The Daily Mirror had sought information under the Right to Information Act at the time of publication, and the cause and losses remained unconfirmed by official sources. Engineers from Japan were asked to inspect the machine.

Plant employees and an electrical superintendent said annual maintenance on the machine was carried out only after about a year and a half, and that the work, which normally takes five to six weeks, was compressed into three weeks. They said an earlier instruction from the Asset Management Unit not to operate the generator without this maintenance was not acted on, and that the schedule was linked to avoiding overtime payments. These are claims by staff and have not been confirmed by the operator or the ministry.

  1. Track overdue major maintenance on generators and do not run machines after an engineering instruction to defer operation until servicing is complete.
  2. Confirm that electrical connections and breaker work are fully completed and checked before a unit is returned to service.
  3. Plan outage windows realistically, because compressed maintenance schedules raise the risk of errors and delayed defect detection.
  4. Make incident records and official responses consistent and documented, so that the cause and losses can be verified independently.

More lessons on maintenance, inspection and ageing assets, electrical protection and isolation, detection and monitoring, from every incident on the register.

Published 2026-11-20. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.