UPS malfunction at Singapore Exchange data centre halts trading

Nov 2014Published 13 Oct 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): Singapore Exchange

On 5 November 2014 the trading systems of the Singapore Exchange (SGX) went down. SGX said the cause was a malfunction in the backup power systems at its primary data centre. The primary data centre is fed by two separate substations, each connected to its own uninterruptible power supply (UPS) system. A momentary fluctuation in the power supply, caused by lightning, should have led the UPS systems to keep the equipment running.

Instead the UPS systems switched to their internal power source, which malfunctioned. SGX said the reason was still unknown. The UPS systems had last been tested in August. Because the disruption was brief and could have caused a mismatch between primary and secondary order books, SGX did not fail over to its secondary data centre. It restarted both primary and secondary systems instead. Recovery was completed at 4.45pm for the securities market and 6pm for the derivatives market.

Lightning caused the initial fluctuation in the power supply. The UPS systems' internal power source malfunctioned for reasons SGX had not determined at the time of reporting. SGX last tested the UPS systems in August 2014.

  1. Test UPS transfer and internal power source performance under realistic fault conditions at regular intervals, and record the results.
  2. Define in advance the criteria for failing over to a secondary site after a transient power disturbance, so that the decision is not taken under pressure during an outage.
  3. Check that UPS transfer logic responds as designed to brief supply fluctuations caused by lightning, and that protection at the incoming supply limits such disturbances.

More lessons on outages, backup supply and restoration, weather and external hazards, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Published 2026-10-13. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Data centre incidents by year, free with a credit (PNG).

Data centre incidents in Singapore: 4 entries, with a free alert for the next one.

See UPS and battery room fires at data centres.

Browse the full register or submit an incident.