Transformer fire disrupts power to Bengaluru's central business district
Feb 2020Published 21 Sept 2026Responsible editor: Chief Editor
- Where
- 66 kV power station at Anand Rao Circle in Bengaluru
- Operator
- Karnataka Power Transmission Corporation Ltd (KPTCL)
- What
- 20 MVA transformer caught fire after breaker failed to trip
- Response
- Fire and Emergency Services took over half an hour
- Cause
- Protection breaker system failed to trip
Get the next one by email
Free alerts on grid infrastructure incidents in India, and an email when EIR-1139 is updated. No account needed; unsubscribe in one click.
Confirm your email and every substation and transformer incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Karnataka Power Transmission
What happened
A fire broke out at the Karnataka Power Transmission Corporation Ltd (KPTCL) 66 kV power station at Anand Rao Circle in Bengaluru. A 20 MVA transformer developed a fault and caught fire after its breaker system failed to trip, and the blaze spread to an adjacent transformer. Fire and Emergency Services took over half an hour to bring the fire under control. Power supply to several areas of the Central Business District, including Vidhana Soudha and Vikasa Soudha government buildings, was affected during an ongoing legislative session.
Supply to Vidhana Soudha was quickly switched to another substation. The two affected transformers, which together carried around 60 MW, were taken out of service for repair or scrapping, with load temporarily redistributed from other stations and short periods of load-shedding expected until a replacement transformer was installed.
Contributing factors
A protection breaker system reportedly failed to trip when the fault occurred, allowing the fire to develop and spread to a neighbouring transformer. The failed transformer was around 24 years old.
Lessons learned
- Protection breaker systems on transformers must be tested regularly so they trip under fault conditions and stop fire from starting.
- Transformers approaching 24 years old should be checked for replacement before faults lead to fire and spread.
- Substations serving critical loads need ready backup routes so supply can be switched quickly during failures.
More lessons on electrical protection and isolation, spacing, layout and fire spread, outages, backup supply and restoration, from every incident on the register.
Not yet known
- Exact cause of the initial fault
- Transformer model and serial number
- Duration of repairs and load shedding
- Cost of damage and supply disruption
This entry is updated when these are reported. Get an alert for the next one like it.
Source