SP Power Grid fined for Carlton Hotel and Bright Hill substation fires
Feb 2019Published 19 Sept 2026Responsible editor: Chief Editor
- Where
- Carlton Hotel and Bright Hill substations, Singapore
- Operator
- SP Power Grid
- What
- two substation fires causing power outages
- Cause
- short circuit after insulation failure and faulty voltage transformer
Get the next one by email
Free alerts on grid infrastructure incidents in Singapore, and an email when EIR-1107 is updated. No account needed; unsubscribe in one click.
Confirm your email and every substation and transformer incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): SP Power Grid
What happened
Singapore's grid operator SP Power Grid (SPPG) was fined a total of $1.75 million by the Energy Market Authority (EMA) for two separate substation fire incidents earlier in 2019. On 14 February, a fire at a substation near Carlton Hotel caused a power disruption in parts of central Singapore, attributed to a short circuit in switchgear after insulation failed due to heat stress from foreign contaminants. On 26 January, a fire at a substation in Bright Hill caused a power outage lasting about ninety minutes, affecting roughly 27,000 residents.
Investigations found the Bright Hill fire was started by a faulty voltage transformer that had been used beyond its manufacturer-recommended lifespan. EMA determined the Carlton Hotel incident could have been prevented had SPPG followed its own monitoring procedures during maintenance work.
Contributing factors
Foreign contaminants introduced during maintenance work led to insulation failure in switchgear at the Carlton Hotel substation, with SPPG found not to have complied with its own standard operating procedure for monitoring such work. At Bright Hill, a voltage transformer had remained in service beyond the manufacturer's recommended lifespan before it failed and caused a fire.
Lessons learned
- Switchgear in substations must be kept free of foreign contaminants during maintenance to avoid insulation failure and short circuits.
- Voltage transformers must be replaced before the end of their manufacturer recommended lifespan to prevent fire.
- Substation operators must follow their own monitoring procedures during maintenance to stop insulation failure.
More lessons on electrical protection and isolation, maintenance, inspection and ageing assets, worker safety and safe systems of work, from every incident on the register.
Not yet known
- Exact age of the voltage transformer
- Model of the switchgear and voltage transformer
- Cost of repairs and lost supply
- Duration of the Carlton Hotel outage
This entry is updated when these are reported. Get an alert for the next one like it.
Published 2026-09-19. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.