Grid infrastructureUnited KingdomEIR-0757

NSL interconnector trip causes GB grid frequency dip, batteries respond

Oct 2024Published 15 Sept 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
supply cut for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden
Where
NSL interconnector, UK to Norway, 8 October 2024
What
Import fell from 1.4 GW to zero, frequency to 49.59 Hz
Injuries
None reported
Response
1.5 GW batteries responded, recovery in two minutes
Cause
Sudden unexplained loss of 1.4 GW import capacity

Companies named in the reporting of this entry (being named is not a finding of fault): National Energy System Operator

On 8 October 2024 at 8:47am local time, the NSL interconnector, which links the UK and Norway, suddenly stopped exporting power, with imports falling from 1.4GW to zero. Grid frequency on the British network fell as low as 49.59Hz within two seconds, breaching the National Energy System Operator's normal operational limits of 49.8 to 50.2Hz. The system recovered within two minutes as fast-acting frequency response services, particularly battery energy storage systems from several operators, injected power into the grid.

Around 1.5GW of batteries across the network responded, including assets optimised by Arenko Group and Kraken, with Kraken-optimised batteries alone delivering over 450MW of response, equivalent to roughly a third of the power lost. No damage, injuries or wider blackout resulted from the event.

Sudden and unexplained loss of 1.4GW of interconnector import capacity from the NSL Link between the UK and Norway.

  1. An interconnector trip can drop 1.4 GW import in seconds and push frequency to 49.59 Hz, so operators must size frequency response to cover full link capacity.
  2. Battery fleets can inject 1.5 GW within seconds, so contracts should require fast response from aggregated assets across multiple optimisers.
  3. A single interconnector outage can be covered when response is spread across operators, so systems should avoid reliance on one asset type or site.

More lessons on investigation and fleet-wide checks, spacing, layout and fire spread, from every incident on the register.

  • Exact cause of the NSL trip
  • Cost of the frequency response services
  • Duration of any resulting market price spike

This entry is updated when these are reported. Get an alert for the next one like it.

Published 2026-09-15. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Grid infrastructure incidents in the United Kingdom, by year, free with a credit (PNG).

Grid infrastructure incidents in the United Kingdom: 117 entries, with a free alert for the next one.

Browse the full register or submit an incident.