Bird-triggered electrical fault sparks fire and major outage at California solar farm
June 2019Published 14 Sept 2026Responsible editor: Chief Editor
- Where
- California Valley Solar Ranch, California
- Owner
- Clearway Energy Inc.
- Manufacturer
- SunPower Corp
- What
- Bird contact with conductors sparked fire and outage
- Injuries
- None reported
Get the next one by email
Free alerts on solar PV incidents in the United States, and an email when EIR-0688 is updated. No account needed; unsubscribe in one click.
Confirm your email and every solar incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
Companies named in the reporting of this entry (being named is not a finding of fault): Clearway Energy, Pacific Gas and Electric, SunPower
What happened
On 5 June 2019 a fire broke out at the California Valley Solar Ranch, a 250 megawatt photovoltaic plant owned by Clearway Energy Inc. A California Department of Forestry and Fire Protection (Cal Fire) official said the fire began when a bird made contact with two overhead conductors simultaneously, completing an electrical circuit and producing a shower of sparks. The resulting fire spread through the surrounding dry grassland, burning approximately 1,127 acres.
The blaze damaged power poles and wires at the facility, knocking out 84 percent of its generating capacity. Clearway initially described the cause as an 'avian incident' without providing further detail. The company estimated losses at between 8 and 9 million US dollars. The plant was built by SunPower Corp, completed in 2013, and sells power to Pacific Gas and Electric. Injuries were not reported.
Contributing factors
A bird contacted two energised conductors at once, creating an electrical arc; dry grassland conditions in the surrounding area allowed the resulting sparks to ignite a large fire that spread beyond the immediate electrical equipment.
Lessons learned
- Overhead conductors at solar farms need bird guards where large birds are active, as contact between two phases creates arcs and sparks.
- Dry grassland around solar sites must have maintained firebreaks, as sparks from electrical faults can ignite large fires.
Not yet known
- Downtime duration after the outage
- Whether bird mitigation was already in place
This entry is updated when these are reported. Get an alert for the next one like it.