Battery module fire contained at Valley Center Battery Storage Project, California

Apr 2022Published 8 Sept 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hiddenAsset hidden years oldThe maker is named in 8 other entries (being named is not a finding of fault)
Where
Valley Center Battery Storage Project, Valley Center, San Diego County, California
Operator
Terra-Gen
What
Small electrical failure in one battery module
Injuries
None reported
Outcome
Event contained to single battery module

Companies named in the reporting of this entry (being named is not a finding of fault): LG Energy Solution, Terra-Gen

A small electrical failure occurred within a single battery module at the Valley Center Battery Storage Project, a recently commissioned lithium-ion battery energy storage facility in Valley Center, San Diego County, California, operated and owned by Terra-Gen, using battery modules manufactured by LG Energy Solution. The fault produced smoke, which triggered the site's fire suppression and detection systems. According to the local fire marshal, the systems operated as designed and the event was contained to a single battery module, described as roughly the size of a DVD case.

An adjacent battery enclosure also shut down automatically after detecting smoke, even though it was not directly affected, which the fire marshal characterised as an overly cautious response. Multiple fire engines from local fire protection districts attended the site as a precaution. No injuries were reported and there was no significant fire beyond the contained module-level event.

An electrical failure within a single battery module produced smoke that activated fire detection and suppression systems; smoke also triggered a conservative automatic shutdown of an adjacent, unaffected enclosure.

  1. Lithium-ion battery modules need smoke detection and suppression sized for module level events so that a fault stays inside one module.
  2. Smoke detection in BESS sites can shut down adjacent enclosures that are not affected, so operators should plan for this loss of availability.
  3. Module level containment reduces the need for external fire crews, so response plans can focus on isolation and exclusion zones.

More lessons on detection and monitoring, fire suppression and firefighting, from every incident on the register.

  • Battery module model and age
  • Duration of site downtime
  • Cost of repairs

This entry is updated when these are reported. Get an alert for the next one like it.

Published 2026-09-08. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Battery storage incidents in the United States, by year, free with a credit (PNG).

Battery storage incidents in the United States: 49 entries, with a free alert for the next one.

Battery storage fires: the counts, the latest entries and a free alert for the next one. Also: battery storage container fires.

Browse the full register or submit an incident.