Khavda grid disturbance removes 8,963 MW of renewables in 16 seconds

May 2026Published 29 Nov 2026Responsible editor: Chief Editor

Companies named in the reporting of this entry (being named is not a finding of fault): Adani Green Energy, NTPC

On 13 May 2026, a transmission line fault at the Khavda renewable energy complex in Gujarat's Kutch region set off a sequence of failures that removed 8,963 MW of renewable generation from India's national grid in 16 seconds. The Business Standard reports that the fault caused sustained voltage fluctuations and that renewable energy inverters responded weakly. The disturbance then led to the cascading tripping of 17 high-capacity transmission lines. Grid frequency fell sharply, triggering automatic protection systems across several regions.

The source describes it as the largest single-event disruption of renewable power of its kind in the country's history. Generation at the complex is operated by Adani Green Energy, NTPC and Gujarat Industries Power Company (GIPCL). A report by an eight-member expert committee appointed by the power ministry has set out the sequence of events, according to the article.

According to the source's account of the expert committee report, a transmission line fault caused sustained voltage fluctuations, weaknesses were exposed in the response of renewable energy inverters, and this led to the cascading tripping of 17 transmission lines. Further contributing factors were not reported.

  1. Inverter-based generation should be tested for ride-through and response to sustained voltage fluctuations, not only to short faults.
  2. Large renewable complexes connected at a single point concentrate risk, so protection coordination across multiple high-capacity lines should be studied for cascading trips.
  3. High-resolution event recording should be fitted at key grid points so that sequences lasting seconds can be reconstructed quickly after a disturbance.

More lessons on electrical protection and isolation, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersLow confidence
supply cut for about •• daysShown in the record →Full estimate

Published 2026-11-29. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Grid infrastructure incidents in India, by year, free with a credit (PNG).

Grid infrastructure incidents in India: 110 entries, with a free alert for the next one.

Browse the full register or submit an incident.