Fire at Machhkund hydropower station damages electrical equipment in Odisha

May 2026Published 18 Nov 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
supply cut for about •• daysShown in the record →Full estimate

A fire broke out at about 12:00 noon on Saturday 23 May 2026 at the Machhkund Hydro Power House at Ankadeli, under Lamtaput Block in Koraput district, Odisha. The 120 MW Machhkund Hydro Electric Project has six generating units, and all six were operational when the fire started. Preliminary reports say a current transformer connected to a 2.5 MVA, 11/0.4 kV transformer outside the powerhouse burst, and the fire spread through connected cables into the cable gallery, damaging several electrical and allied items.

The units were shut down and all personnel were evacuated without injury. Powerhouse staff and the Fire Services team from Lamtaput brought the fire under control, and it was fully extinguished by 4:00 PM. APGENCO officials will carry out a detailed damage assessment, and preliminary estimates suggest restoration may take more than six months.

Preliminary reports attribute the fire to the bursting of a current transformer on a transformer situated outside the powerhouse. The fire then spread through connected cables into the cable gallery. No other contributing factors are reported.

  1. Inspect current transformers and their terminations on external transformers that feed local supplies, since a failed CT can start a fire that spreads into generating plant.
  2. Fit fire barriers and segregation in cable galleries so that a fault in one circuit cannot carry into generating equipment.
  3. Keep unit shutdown and evacuation procedures rehearsed; in this incident all personnel were evacuated without injury.

More lessons on spacing, layout and fire spread, worker safety and safe systems of work, from every incident on the register.

Published 2026-11-18. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Grid infrastructure incidents in India, by year, free with a credit (PNG).

Grid infrastructure incidents in India: 102 entries, with a free alert for the next one.

Substation and transformer fires: the counts, the latest entries and a free alert for the next one. Also: power line and cable failures.

Browse the full register or submit an incident.