Arc flash damages battery cabinet at Cyxtera BOS1 in Waltham

Feb 2023Published 2 Oct 2026Responsible editor: Chief Editor

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Companies named in the reporting of this entry (being named is not a finding of fault): Cyxtera

On 14 February 2023, firefighters were called to an electrical equipment fire at Cyxtera BOS1 in Waltham, Massachusetts. An explosion and arc flash in a battery cabinet damaged that cabinet and adjacent cabinets when panels were blown off. Smoke detectors and the fire alarm operated. Fire services evacuated the building, had power shut down, and ventilated the premises after hazardous levels of carbon monoxide and hydrogen cyanide were found. One person was taken to hospital with possible smoke inhalation. The building was reported undamaged, and fire services later allowed operations to resume the same day.

The fire department report states that the cause is undetermined. Investigators considered it most likely that an unspecified electrical event tripped a breaker under load, after which generator power automatically back-fed the main breaker and caused it to arc and burn inside the cabinet. Work on another electrical service in the same room was reported as appearing unrelated.

  1. Check that standby generators cannot back-feed a breaker that has tripped under fault, and test that protection.
  2. Keep the recorded cause open when investigators say it is undetermined, even if a most-likely electrical sequence is described.
  3. Do not allow re-entry until ventilation has reduced carbon monoxide and hydrogen cyanide after a battery-cabinet arc event.

More lessons on electrical protection and isolation, investigation and fleet-wide checks, from every incident on the register.

Other entries that name Waltham

Published 2026-10-02. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Battery storage incidents in the United States, by year, free with a credit (PNG).

Battery storage incidents in the United States: 52 entries, with a free alert for the next one.

Battery storage fires: the counts, the latest entries and a free alert for the next one. Also: battery storage container fires and battery storage explosions.

Browse the full register or submit an incident.