Structural failure of HDPE floats at Itumbiara floating solar plant, Brazil

2025Published 30 Nov 2026Responsible editor: Chief Editor

A study by researchers from the Federal University of Rio de Janeiro (UFRJ) and Brazil's Electric Energy Research Center (Cepel) examined high-density polyethylene (HDPE) floats from the Itumbiara and Sobradinho floating PV plants after about five years of operation. The Itumbiara floating array, a 200 kW system deployed alongside an 800 kW ground-mounted PV system on the Itumbiara hydropower reservoir, suffered a structural failure that partially submerged the installation. The date of the failure is not reported in the source.

Reported damage included perforations, fractured floats, and failures of mechanical connections and anchoring elements. The researchers examined flat and concave components recovered after the failure. The tested concave component showed about 40% lower maximum tensile stress than an unaged Sobradinho reference. The researchers could not determine whether these differences arose from material selection, manufacturing or environmental degradation, because no unaged Itumbiara samples or original resin specifications were available. The findings were published in Engineering Failure Analysis.

The researchers could not establish whether material selection, manufacturing processes or environmental degradation contributed to the failure. They noted that UV exposure, temperature fluctuations, wind, waves and water can compromise HDPE, but the study did not confirm these as the cause at Itumbiara.

  1. Floating PV procurement should require original resin specifications and manufacturing records, so that later failures can be traced to material, process or environment.
  2. Accelerated laboratory ageing may not reproduce combined field stresses, so retrieval and inspection of floats after several years is valuable.
  3. Mechanical connections and anchoring elements should be inspected as carefully as the floats.

More lessons on design, standards and commissioning, maintenance, inspection and ageing assets, electrical protection and isolation, from every incident on the register.

Estimated damageEstimated by the register's adjusterHow? Know the real figure?
Figure hidden: shown to subscribersMedium confidence
out of service for about •• daysShown in the record →Full estimate
From the recordRoot cause hiddenFailed part hidden

Published 2026-11-30. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.

See the register's stories first in Google: add it as a preferred source.

Chart to reuse with this story: Solar PV incidents in Brazil, by year, free with a credit (PNG).

Solar PV incidents in Brazil: 20 entries, with a free alert for the next one.

Solar farm fires: the counts, the latest entries and a free alert for the next one.

Browse the full register or submit an incident.