Testing fault at 100 MW battery disrupts Estonia-Finland power link
Jan 2026Published 28 Nov 2026Responsible editor: Chief Editor
Get the next one by email
Free alerts on battery storage incidents worldwide, and an email when EIR-3082 is updated. No account needed; unsubscribe in one click.
Confirm your email and every battery storage incident on the register arrives at once as a spreadsheet (CSV), free.
Get a free sample brief Three complete verified records and the incidents-per-GW table, by email within a minute.
We will also email you about the register's paid records and plans, at most once a week and three times in all. You can stop these at any time. By signing up you agree to the privacy policy.
What happened
On 20 January 2026, a disturbance in Estonia's power system caused both EstLink connections between Estonia and Finland to shut down, a loss of roughly 1,000 MW, about 20% of the Baltic region's winter electricity load. The oscillations were reported to have been triggered by a 100 MW/200 MWh battery energy storage system at Kiisa, south of Tallinn, during final grid connection testing, which caused the DC cables to trip.
The shortfall was first covered by the continental European grid, with the 500 MW Poland-Lithuania AC link running at double its rated capacity, and later by reserve capacity within the Baltic states. Elering, the transmission system operator, said the oscillation came from a device connected to the main grid whose behaviour did not comply with network requirements. The developer, Evecon, confirmed the device belonged to the Kiisa project and said the fault occurred during configuration and testing, not regular operation.
Contributing factors
Elering stated that the device's behaviour did not comply with network requirements. Evecon said the fault occurred during configuration and testing, and that the system manufacturer, Nidec Conversion, was responsible for the testing phase until final commissioning. Elering said the growing number of inverter-based devices on the network is a concern for the Baltic system following desynchronisation from the Russian grid.
Lessons learned
- Verify that inverter-based storage meets grid-code and oscillation-damping requirements before live grid connection tests begin.
- Agree commissioning test sequences and stop criteria with the transmission operator in advance, so that a fault can be contained quickly.
- Define in contracts who holds responsibility for the plant during testing, between developer, manufacturer and grid operator.
- Assess system-wide oscillation risk as inverter-based resources grow, particularly in systems recently separated from neighbouring grids.
More lessons on electrical protection and isolation, design, standards and commissioning, emergency response and public communication, from every incident on the register.
Source
Published 2026-11-28. Written from public reporting. Descriptive, not investigative. See the data accuracy disclaimer.