A battery storage loan is priced on a fleet nobody has seen fail. The public record shows what did fail, where, and what followed. This report puts that record in the order a lender asks the questions.

191
battery storage incidents on the register
87%
fires or thermal events
16 weeks
typical time out of service
typical loss per incident

See all 25 blurred figures in this report

The trendReported battery incidents by year since 2020

35 so far in 2026 against 29 in 2025. Counts of published reporting, so they rise with the fleet and with how much gets reported, not with failure rates alone.

20202
20219
202221
202332
202424
202529
202635
YearIncidentsFiresMajor
2020222
2021993
202221172
202332273
202424233
202529241
202635280

Peer comparisonIncidents per GW of operating battery capacity, by country

Entries since 2020 against the operating battery capacity the register's site list holds for each country (the planning database in Great Britain, EIA-860 in the United States, ODRE in France and the Global Energy Monitor elsewhere). Countries with at least 0.5 GW listed and three entries. A rate, not a probability: the fleet and the reporting both differ by country.

1.1
10th percentile, incidents per GW
2.2
median country
3.2
90th percentile
CountryGW listedIncidentsPer GW
Australia2.073.5
United Kingdom5.0132.6
France2.341.7
United States56.750

Subscribers Blurred figures are in the subscriber edition. See the plans.

Where a fleet sits against these figures is one question a lender can now ask with a number in hand.

What failsThe part named most often

Of the battery entries whose full record names the part that failed (131), these are named most often.

PartEntriesShare
battery energy storage system32%
not reported22%

Subscribers Blurred figures are in the subscriber edition. See the plans.

WhenCommissioning against normal operation

Of the 152 battery entries with a stage of life recorded:

Commissioning18
Normal operation132
Maintenance1
End-of-life1

Contracts and policies concentrate on commissioning. The record shows where the incidents actually sit.

Time out and lossHow long a battery site is out, and what it costs

From the loss and downtime estimate on every entry (191 battery incidents), counted at the middle of each range; a figure a source states always wins. The full method is in the loss and downtime benchmarks.

MeasureTypical90th pct
Time out of service16 weeks
Loss per incident
Out for more than 30 days
Out for more than 90 days

Subscribers Blurred figures are in the subscriber edition. See the plans.

Due diligenceSix questions to ask a borrower, each with a number behind it

  1. Which cells, modules and integrator are in the system, and have any of them been named in a published incident? The register lists every company named in its entries, and a counterparty check takes a minute.
  2. What protects the battery energy storage system? It is the part most often named in the battery entries that record one (3 of 131).
  3. What does the commissioning plan say about energisation, state-of-charge limits and fire-service liaison? 12% of the battery incidents with a stage recorded happened during commissioning.
  4. What is the business interruption waiting period, and does the model survive 16 weeks out of service? That is the typical time out for a battery incident on the register, and 78% of them ran past 30 days.
  5. How does the site's country compare? Incidents per GW in this report range from 1.1 to 3.2 across the countries with enough entries to count, so a fleet's record should be read against its own market, not the world.
  6. Who is told when the register records an incident at this site, or at a site with the same equipment? A free account watches three sites; the plans watch every site in a portfolio.

Subscriber editionWhat the full report adds

  • Subscribers Every country's incidents and fires per GW, not only the top three.
  • Subscribers The full ranking of failed parts, and the loss and time out in pounds and days with the 90th percentiles.
  • Subscribers The largest estimated battery losses of the last two years, each linked to its entry.
  • Subscribers My sites: a portfolio's sites checked against every entry, an email the moment a new one is published, and the live outage notices at each site.

See the plans. A free account watches three sites; Analyst includes this report and every record, at £39 a month.

What this report is not

It is a reading of reported incidents, not a failure rate. The per-GW figures use the capacity the register's site list holds for each country, which is not the whole fleet everywhere, and reporting differs by country and by year.

Most loss and downtime figures are estimates, each a range counted at its middle. The register grows daily, so the figures will move. Nothing here is advice; it is the record, in order.